SA4310
Flow sensor. SAEXXXXBFRKG/US-100
Measurement of flow and temperature at the same time. Optimised for water, oils and air. Red/green display for clear identification of the acceptable range. With switching output, analogue signal and IO-Link. The process connection can be rotated for optimum alignment
| Number of inputs and outputs: | Number of digital outputs: 2; Number of analogue outputs: 1 |
| Process connection: | diameter Ø 8 mm |
| Measuring range [°F]: | -4...212 |
| Special feature: | Gold-plated contacts |
| Media: | water; glycol solutions; air; oils |
| Note on media: | low-viscosity oils with viscosity: ≤ 40 mm²/s (104 °F) high-viscosity oils with viscosity: > 40 mm²/s (104 °F) |
| Medium temperature [°F]: | -4...212 |
| Pressure rating [bar]: | 50 |
| Pressure rating [psi]: | 725 |
| MAWP (for applications according to CRN) [bar]: | 50 |
| Operating voltage [V]: | 18...30 DC |
| Current consumption [mA]: | < 100 |
| Protection class: | III |
| Reverse polarity protection: | yes |
| Power-on delay time [s]: | 10 |
| Number of inputs and outputs: | Number of digital outputs: 2; Number of analogue outputs: 1 |
| Total number of outputs: | 2 |
| Output signal: | switching signal; analogue signal; frequency signal; IO-Link; (configurable) |
| Electrical design: | PNP/NPN |
| Number of digital outputs: | 2 |
| Output function: | normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC [V]: | 2.5 |
| Permanent current rating of switching output DC [mA]: | 250 |
| Number of analogue outputs: | 1 |
| Analogue current output [mA]: | 4...20; (scalable) |
| Max. load [Ω]: | 350 |
| Short-circuit protection: | yes |
| Type of short-circuit protection: | pulsed |
| Overload protection: | yes |
| Frequency of the output [Hz]: | 0...1000 |
| Probe length L [mm]: | 200 |
| Operating mode: | relative; absolutely liquid; absolutely gaseous; (absolute: reference measurement recommended) |
| Note on factory setting: | Operating mode: relative |
| Setting range [ft/s]: | 0...19.5 |
| Greatest sensitivity [ft/s]: | 0.15...9.85 |
| Setting range [ft/s]: | 0...656 |
| Greatest sensitivity [ft/s]: | 6...328 |
| Measuring range [°F]: | -4...212 |
| Resolution [°F]: | 0.5 |
| Temperature drift [cm/s x 1/K]: | 0,01 fps x 1/K (< 68 °F; > 158 °F) |
| Temperature gradient [K/min]: | 100 |
| Accuracy: | ± (7 % MW + 2 % MEW); (for relative mode in the range of maximum sensitivity under the following conditions :; water: 68...158 °F; inlet length: 5 ft; DN25 (DIN 2448); mounting position according to instructions; Accuracy can differ for other media and mounting positions.) |
| Repeatability: | 0,05 m/s; (water; flow velocity: 0,05...3 m/s) |
| Temperature drift: | ± 0,003 K/°F |
| Accuracy [K]: | ± 0,3 / ± 1; (water; flow velocity: 1...9,85 fps / air; flow velocity: > 32,8 fps) |
| Response time [s]: | 0.5; (T09; water; glycol: 0,8 s; air: 7 s; oil: 1,8 s; each T09) |
| Dynamic response T05 / T09 [s]: | 1,5 (T09); (water; flow velocity: 1...9,85 fps) |
| Parameter setting options: | hysteresis / window; normally open / normally closed; switching logic; current/frequency output; medium selection; Damping; Teach function; display can be rotated and switched off; standard unit of measurement; process value colour |
| Communication interface: | IO-Link |
| Transmission type: | COM2 (38,4 kBaud) |
| IO-Link revision: | 1.1 |
| SDCI standard: | IEC 61131-9 |
| IO-Link device ID: | 537 d / 00 02 19 h (REL) |
| Profiles: | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
| SIO mode: | yes |
| Required master port type: | A |
| Process data analogue: | 2 |
| Process data binary: | 2 |
| Min. process cycle time [ms]: | 3 |
| Ambient temperature [°F]: | -40...176 |
| Storage temperature [°F]: | -40...212 |
| Protection: | IP 65; IP 67 |
| EMC: | DIN EN 60947-5-9 |
| Shock resistance: | DIN EN 60068-2-27 50 g (11 ms) |
| DIN EN 60068-2-27: | 50 g (11 ms) |
| Vibration resistance: | DIN EN 60068-2-6 2 g (10...2000 Hz) |
| DIN EN 60068-2-6: | 2 g (10...2000 Hz) |
| MTTF [years]: | 143 |
| UL approval: | UL Approval no. I017 File number UL E174189 |
| UL Approval no.: | I017 |
| File number UL: | E174189 |
| Weight [g]: | 344.5 |
| Materials: | stainless steel (1.4404 / 316L); PBT-GF20; PBT-GF30 |
| Materials (wetted parts): | stainless steel (1.4404 / 316L) |
| Process connection: | diameter Ø 8 mm |
| Display: | Display unit 6 x LED, green (%, fps, gpm, cfm, °F, 10³) switching status 2 x LED, yellow measured values alphanumeric display, red/green 4-digit |
| Display unit: | 6 x LED, green (%, fps, gpm, cfm, °F, 10³) |
| switching status: | 2 x LED, yellow |
| measured values: | alphanumeric display, red/green 4-digit |
| Remarks: | MW = measured value MEW = Final value of the measuring range 544 d / 00 02 20 h (LIQU) 551 d / 00 02 27 h (GAS) |
| Pack quantity: | 1 pcs. |
| Connection: | Connector: 1 x M12; Contacts: gold-plated |
| ECCN: | |
| Country of Origin: | DE |
| EAN: | |
| Weight: | 0.34 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |