PQ3809
Pressure sensor for pneumatics. PQ-1-1-KHR18-KFPKG/AS/
Reliable monitoring of the system pressure in pneumatics and in compressed air systems. Very high overpressure and vacuum resistance. Clearly visible slanted LED display. Red/green display for clear identification of the acceptable range. With programmable switching output and analogue output
| Output signal: | switching signal; analogue signal; IO-Link; (configurable) |
| Measuring range: | -1...1 bar -1000...1000 mbar -14.6...14.6 psi -29.4...29.4 inHg -100...100 kPa |
| -1...1 bar: | -1000...1000 mbar |
| Process connection: | threaded connection G 1/8 internal thread internal thread:M5 |
| Special feature: | Gold-plated contacts |
| Application: | for industrial applications |
| Conditionally suitable for: | other media on request |
| Medium temperature [°C]: | 0...60 |
| Min. bursting pressure: | 30 bar 435 psi 886 inHg 3000 kPa |
| 30 bar: | 435 psi |
| Note on min. burst pressure: | max. overpressure on second pressure connection: 12 bar / 1200 kPa / 174 PSI / 354,4 inHg / 1,2 MPa |
| Pressure rating: | 20 bar 290 psi 591 inHg 2000 kPa |
| 20 bar: | 290 psi |
| Vacuum resistance [mbar]: | -1000 |
| Type of pressure: | relative pressure; differential pressure; vacuum |
| Operating voltage [V]: | 18...32 DC; (according to EN 50178 SELV/PELV) |
| Current consumption [mA]: | < 50 |
| Min. insulation resistance [MΩ]: | 100; (500 V DC) |
| Protection class: | III |
| Reverse polarity protection: | yes |
| Overvoltage protection: | yes; (< 40 V) |
| Power-on delay time [s]: | 0.5 |
| Integrated watchdog: | yes |
| Number of inputs and outputs: | Number of digital outputs: 1; Number of analogue outputs: 1 |
| Total number of outputs: | 2 |
| Output signal: | switching signal; analogue signal; IO-Link; (configurable) |
| Electrical design: | PNP |
| Number of digital outputs: | 1 |
| Output function: | normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC [V]: | 2 |
| Permanent current rating of switching output DC [mA]: | 100 |
| Switching frequency DC [Hz]: | < 100 |
| Number of analogue outputs: | 1 |
| Analogue current output [mA]: | 4...20 |
| Max. load [Ω]: | 500 |
| Short-circuit protection: | yes |
| Type of short-circuit protection: | pulsed |
| Measuring range: | -1...1 bar -1000...1000 mbar -14.6...14.6 psi -29.4...29.4 inHg -100...100 kPa |
| -1...1 bar: | -1000...1000 mbar |
| Set point SP: | -0.98...1 bar -14.2...14.6 psi -28.8...29.4 inHg -98...100 kPa |
| -0.98...1 bar: | -14.2...14.6 psi |
| Reset point rP: | -0.99...0.99 bar -14.4...14.4 psi -29.1...29.1 inHg -99...99 kPa |
| -0.99...0.99 bar: | -14.4...14.4 psi |
| In steps of: | 0.01 bar 0.2 psi 0.3 inHg 1 kPa |
| 0.01 bar: | 0.2 psi |
| Switch point accuracy [% of the span]: | < ± 0,5 |
| Repeatability [% of the span]: | < ± 0,1; (with temperature fluctuations < 10 K) |
| Characteristics deviation [% of the span]: | < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting) |
| Hysteresis deviation [% of the span]: | < ± 0,25 |
| Long-term stability [% of the span]: | < ± 0,05; (per 6 months) |
| Temperature coefficient zero point [% of the span / 10 K]: | 0,2; (0...60 °C) |
| Temperature coefficient span [% of the span / 10 K]: | 0,2; (0...60 °C) |
| Response time [ms]: | < 6 |
| Delay time programmable dS, dr [s]: | 0; 0,002...5 |
| Step response time analogue output [ms]: | 6 |
| Parameter setting options: | hysteresis / window; normally open / normally closed; analogue output; IO-Link; switching logic; switch-on/switch-off delay; Damping; Display unit |
| Communication interface: | IO-Link |
| Transmission type: | COM2 (38,4 kBaud) |
| IO-Link revision: | 1.1 |
| SDCI standard: | IEC 61131-9 FDIS |
| IO-Link device ID: | 366 d / 00 01 6E h |
| Profiles: | Smart Sensor: Process Data Variable; Device Identification |
| SIO mode: | yes |
| Required master port type: | A |
| Process data analogue: | 1 |
| Process data binary: | 2 |
| Min. process cycle time [ms]: | 2.3 |
| Ambient temperature [°C]: | 0...70 |
| Storage temperature [°C]: | -25...85 |
| Protection: | IP 65 |
| EMC: | DIN EN 61000-6-2 DIN EN 61000-6-3 |
| Shock resistance: | DIN EN 60068-2-27 50 g (11 ms) |
| DIN EN 60068-2-27: | 50 g (11 ms) |
| Vibration resistance: | DIN EN 60068-2-6 20 g (10...2000 Hz) |
| DIN EN 60068-2-6: | 20 g (10...2000 Hz) |
| MTTF [years]: | 437 |
| Pressure Equipment Directive: | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
| Weight [K40]: | 86.5 |
| Materials: | PBT; FKM; polyester |
| Materials (wetted parts): | brass; FKM; silicon (coated); PBT |
| Min. pressure cycles: | 50 million |
| Process connection: | threaded connection G 1/8 internal thread internal thread:M5 |
| Display: | Display unit 4 x LED, green switching status 1 x LED, yellow function display alphanumeric display, 4-digit measured values alphanumeric display, 4-digit |
| Display unit: | 4 x LED, green |
| switching status: | 1 x LED, yellow |
| function display: | alphanumeric display, 4-digit |
| measured values: | alphanumeric display, 4-digit |
| Display unit: | bar; kPa; psi; inHg |
| Pack quantity: | 1 pcs. |
| Connection: | Connector: 1 x M8; Contacts: gold-plated |
| ECCN: | |
| Country of Origin: | RO |
| EAN: | |
| Weight: | 0.09 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |