PN2293
Pressure sensor with display. PN-025-REN14-MFRKG/US/ /V
Programmable switching output with IO-Link and scalable analogue output. Red/green display for clear identification of the acceptable range. The process connection can be rotated for optimum alignment. With long-term stability thanks to high overload protection. Robust design for use in harsh industrial environments
Output signal: | switching signal; analogue signal; IO-Link; (configurable) |
Measuring range: | -1...25 bar -14.5...362.5 psi -0.1...2.5 MPa |
-1...25 bar: | -14.5...362.5 psi |
Process connection: | threaded connection 1/4" NPT internal thread |
Special feature: | Gold-plated contacts |
Measuring element: | ceramic-capacitive pressure measuring cell |
Application: | for industrial applications |
Media: | liquids and gases |
Medium temperature [°C]: | -25...80 |
Min. bursting pressure: | 350 bar 5075 psi 35 MPa |
350 bar: | 5075 psi |
Pressure rating: | 150 bar 2175 psi 15 Mpa |
150 bar: | 2175 psi |
Vacuum resistance [mbar]: | -1000 |
Type of pressure: | relative pressure; vacuum |
MAWP (for applications according to CRN): | 70 bar 1015 psi 7 MPa |
70 bar: | 1015 psi |
Operating voltage [V]: | 18...30 DC; (according to EN 50178 SELV/PELV) |
Current consumption [mA]: | < 35 |
Min. insulation resistance [MΩ]: | 100; (500 V DC) |
Protection class: | III |
Reverse polarity protection: | yes |
Power-on delay time [s]: | 0.3 |
Integrated watchdog: | yes |
Number of inputs and outputs: | Number of digital outputs: 2; Number of analogue outputs: 1 |
Total number of outputs: | 2 |
Output signal: | switching signal; analogue signal; IO-Link; (configurable) |
Electrical design: | PNP/NPN |
Number of digital outputs: | 2 |
Output function: | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V]: | 2 |
Permanent current rating of switching output DC [mA]: | 250 |
Switching frequency DC [Hz]: | < 500 |
Number of analogue outputs: | 1 |
Analogue current output [mA]: | 4...20; (scalable 1:5) |
Max. load [Ω]: | 500 |
Analogue voltage output [V]: | 0...10; (scalable 1:5) |
Min. load resistance [Ω]: | 2000 |
Short-circuit protection: | yes |
Type of short-circuit protection: | pulsed |
Overload protection: | yes |
Measuring range: | -1...25 bar -14.5...362.5 psi -0.1...2.5 MPa |
-1...25 bar: | -14.5...362.5 psi |
Set point SP: | -0.85...25 bar -12...362.5 psi -0.085...2.5 MPa |
-0.85...25 bar: | -12...362.5 psi |
Reset point rP: | -0.95...24.9 bar -13.5...361 psi -0.095...2.49 MPa |
-0.95...24.9 bar: | -13.5...361 psi |
Analogue start point: | -1...20 bar -14.5...290 psi -0.1...2 MPa |
-1...20 bar: | -14.5...290 psi |
Analogue end point: | 4...25 bar 58...362.5 psi 0.4...2.5 MPa |
4...25 bar: | 58...362.5 psi |
In steps of: | 0.05 bar 0.5 psi 0.005 MPa |
0.05 bar: | 0.5 psi |
Switch point accuracy [% of the span]: | < ± 0,4; (Turn down 1:1) |
Repeatability [% of the span]: | < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1) |
Characteristics deviation [% of the span]: | < ± 0,25 (BFSL) / < ± 0,5 (LS); (Turn down 1:1; BFSL = Best Fit Straight Line; LS = limit value setting) |
Hysteresis deviation [% of the span]: | < ± 0,1; (Turn down 1:1) |
Long-term stability [% of the span]: | < ± 0,05; (Turn down 1:1; per 6 months) |
Temperature coefficient zero point [% of the span / 10 K]: | < ± 0,2; (-0...80 °C) |
Temperature coefficient span [% of the span / 10 K]: | < ± 0,2; (-0...80 °C) |
Response time [ms]: | < 1.5 |
Delay time programmable dS, dr [s]: | 0...50 |
Damping for the switching output dAP [s]: | 0...4 |
Damping for the analogue output dAA [s]: | 0...4 |
Max. response time analogue output [ms]: | 3 |
Parameter setting options: | hysteresis / window; normally open / normally closed; switch-on/switch-off delay; Damping; Display unit; current/voltage output |
Communication interface: | IO-Link |
Transmission type: | COM2 (38,4 kBaud) |
IO-Link revision: | 1.1 |
SDCI standard: | IEC 61131-9 |
IO-Link device ID: | 472 d / 00 01 d8 h |
Profiles: | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
SIO mode: | yes |
Required master port type: | A |
Process data analogue: | 1 |
Process data binary: | 2 |
Min. process cycle time [ms]: | 2.3 |
Ambient temperature [°C]: | -25...80 |
Storage temperature [°C]: | -40...100 |
Protection: | IP 65; IP 67 |
EMC: | DIN EN 61000-6-2 DIN EN 61000-6-3 |
Shock resistance: | DIN EN 60068-2-27 50 g (11 ms) |
DIN EN 60068-2-27: | 50 g (11 ms) |
Vibration resistance: | DIN EN 60068-2-6 20 g (10...2000 Hz) |
DIN EN 60068-2-6: | 20 g (10...2000 Hz) |
MTTF [years]: | 138 |
UL approval: | UL Approval no. J012 |
UL Approval no.: | J012 |
Pressure Equipment Directive: | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
Weight [g]: | 223.5 |
Materials: | stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC |
Materials (wetted parts): | stainless steel (1.4404 / 316L); AI2O3 (96%; ceramics); FKM |
Min. pressure cycles: | 100 million |
Tightening torque [Nm]: | > 50; (depends on lubrication, seal and pressure rating) |
Process connection: | threaded connection 1/4" NPT internal thread |
Restrictor element integrated: | no (can be retrofitted) |
Display: | Display unit 3 x LED, green (bar, psi, MPa) switching status 2 x LED, yellow measured values alphanumeric display, red/green 4-digit |
Display unit: | 3 x LED, green (bar, psi, MPa) |
switching status: | 2 x LED, yellow |
measured values: | alphanumeric display, red/green 4-digit |
Pack quantity: | 1 pcs. |
Connection: | Connector: 1 x M12; Contacts: gold-plated |
ECCN: | |
Country of Origin: | DE |
EAN: | |
Weight: | 0.22 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |