Ifm PN2224

Pressure sensor with display. PN-010-RBN14-MFRKG/US/ /V

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

Two switching outputs, one of them programmable as analogue output. Clearly visible 4-digit LED display. Country-specific pressure units selectable. With long-term stability thanks to high overload protection. Selectable output polarity

Technical parameters

Output signal: switching signal; analogue signal; IO-Link; (configurable)
Measuring range: -1...10 bar -14.5...145 psi -100...1000 kPa -0.1...1 MPa
-1...10 bar: -14.5...145 psi
Process connection: threaded connection 1/4" NPT internal thread
Special feature: Gold-plated contacts
Application: for industrial applications
Media: liquids and gases
Medium temperature [°C]: -25...80
Min. bursting pressure: 150 bar 2175 psi 15 MPa
150 bar: 2175 psi
Pressure rating: 75 bar 1088 psi 7.5 Mpa
75 bar: 1088 psi
Type of pressure: relative pressure
MAWP (for applications according to CRN): 39 bar 565 psi 3.9 MPa
39 bar: 565 psi
Operating voltage [V]: 18...32 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA]: < 35
Min. insulation resistance [MΩ]: 100; (500 V DC)
Protection class: III
Reverse polarity protection: yes
Power-on delay time [s]: 0.3
Integrated watchdog: yes
Number of inputs and outputs: Number of digital outputs: 2; Number of analogue outputs: 1
Total number of outputs: 2
Output signal: switching signal; analogue signal; IO-Link; (configurable)
Electrical design: PNP/NPN
Number of digital outputs: 2
Output function: normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V]: 2
Permanent current rating of switching output DC [mA]: 250
Switching frequency DC [Hz]: < 500
Number of analogue outputs: 1
Analogue current output [mA]: 4...20; (scalable 1:4)
Max. load [Ω]: (Ub - 10 V) x 50
Analogue voltage output [V]: 0...10; (scalable 1:4)
Min. load resistance [Ω]: 2000
Short-circuit protection: yes
Type of short-circuit protection: pulsed
Overload protection: yes
Measuring range: -1...10 bar -14.5...145 psi -100...1000 kPa -0.1...1 MPa
-1...10 bar: -14.5...145 psi
Set point SP: -0.88...10 bar -12.8...145 psi -0.088...1 MPa
-0.88...10 bar: -12.8...145 psi
Reset point rP: -0.94...9.94 bar -13.6...144.2 psi > -0.094 MPa
-0.94...9.94 bar: -13.6...144.2 psi
Analogue start point: -1...7.26 bar -14.6...105.2 psi -0.1...0.726 MPa
-1...7.26 bar: -14.6...105.2 psi
Analogue end point: 21.8...145 psi 0.15...1 MPa
21.8...145 psi: 0.15...1 MPa
In steps of: 0.02 bar 0.29 psi 0.002 MPa
0.02 bar: 0.29 psi
Factory setting: SP1 = 36.2 psi rP1 = 33.4 psi SP2 = 108.8 psi rP2 = 105.8 psi ASP = 0.0 psi AEP = 145.0 psi
Switch point accuracy [% of the span]: < ± 0,4; (Turn down 1:1)
Repeatability [% of the span]: < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1)
Characteristics deviation [% of the span]: < ± 0,25 (BFSL) / < ± 0,5 (LS); (Turn down 1:1; BFSL = Best Fit Straight Line; LS = limit value setting)
Hysteresis deviation [% of the span]: < ± 0,1; (Turn down 1:1)
Long-term stability [% of the span]: < ± 0,1; (Turn down 1:1; per year)
Temperature coefficient zero point [% of the span / 10 K]: < ± 0,2; (-25...80 °C)
Temperature coefficient span [% of the span / 10 K]: < ± 0,2; (-25...80 °C)
Response time [ms]: < 1.5
Damping for the switching output dAP [s]: 0.01...4
Damping for the analogue output dAA [s]: 0.01...4
Max. response time analogue output [ms]: 3
Parameter setting options: hysteresis / window; normally open / normally closed; switching logic; current/voltage output; Damping; adaptation of displayed values; display can be rotated and switched off; Display unit; zero point; span
Communication interface: IO-Link
Transmission type: COM2 (38,4 kBaud)
IO-Link revision: 1.0
Ambient temperature [°C]: -25...80
Storage temperature [°C]: -40...100
Protection: IP 65
EMC: DIN EN 61000-6-2 DIN EN 61000-6-3
Shock resistance: DIN EN 60068-2-27 50 g (11 ms)
DIN EN 60068-2-27: 50 g (11 ms)
Vibration resistance: DIN EN 60068-2-6 20 g (10...2000 Hz)
DIN EN 60068-2-6: 20 g (10...2000 Hz)
MTTF [years]: 131
Pressure Equipment Directive: Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Weight [g]: 265
Materials: stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); PC; PBT; PEI; FKM; PTFE
Materials (wetted parts): stainless steel (1.4305 / 303); ceramics; FKM
Min. pressure cycles: 100 million
Process connection: threaded connection 1/4" NPT internal thread
Restrictor element integrated: no (can be retrofitted)
Display: Display unit 3 x LED, green switching status 2 x LED, yellow function display alphanumeric display, 4-digit measured values alphanumeric display, 4-digit
Display unit: 3 x LED, green
switching status: 2 x LED, yellow
function display: alphanumeric display, 4-digit
measured values: alphanumeric display, 4-digit
Notes: discontinued article
Pack quantity: 1 pcs.
Connection: Connector: 1 x M12; Contacts: gold-plated

Logistic parameters

ECCN:
Country of Origin: RO
EAN:
Weight: 0.27 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m