PN2224
Pressure sensor with display. PN-010-RBN14-MFRKG/US/ /V
Two switching outputs, one of them programmable as analogue output. Clearly visible 4-digit LED display. Country-specific pressure units selectable. With long-term stability thanks to high overload protection. Selectable output polarity
Output signal: | switching signal; analogue signal; IO-Link; (configurable) |
Measuring range: | -1...10 bar -14.5...145 psi -100...1000 kPa -0.1...1 MPa |
-1...10 bar: | -14.5...145 psi |
Process connection: | threaded connection 1/4" NPT internal thread |
Special feature: | Gold-plated contacts |
Application: | for industrial applications |
Media: | liquids and gases |
Medium temperature [°C]: | -25...80 |
Min. bursting pressure: | 150 bar 2175 psi 15 MPa |
150 bar: | 2175 psi |
Pressure rating: | 75 bar 1088 psi 7.5 Mpa |
75 bar: | 1088 psi |
Type of pressure: | relative pressure |
MAWP (for applications according to CRN): | 39 bar 565 psi 3.9 MPa |
39 bar: | 565 psi |
Operating voltage [V]: | 18...32 DC; (according to EN 50178 SELV/PELV) |
Current consumption [mA]: | < 35 |
Min. insulation resistance [MΩ]: | 100; (500 V DC) |
Protection class: | III |
Reverse polarity protection: | yes |
Power-on delay time [s]: | 0.3 |
Integrated watchdog: | yes |
Number of inputs and outputs: | Number of digital outputs: 2; Number of analogue outputs: 1 |
Total number of outputs: | 2 |
Output signal: | switching signal; analogue signal; IO-Link; (configurable) |
Electrical design: | PNP/NPN |
Number of digital outputs: | 2 |
Output function: | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V]: | 2 |
Permanent current rating of switching output DC [mA]: | 250 |
Switching frequency DC [Hz]: | < 500 |
Number of analogue outputs: | 1 |
Analogue current output [mA]: | 4...20; (scalable 1:4) |
Max. load [Ω]: | (Ub - 10 V) x 50 |
Analogue voltage output [V]: | 0...10; (scalable 1:4) |
Min. load resistance [Ω]: | 2000 |
Short-circuit protection: | yes |
Type of short-circuit protection: | pulsed |
Overload protection: | yes |
Measuring range: | -1...10 bar -14.5...145 psi -100...1000 kPa -0.1...1 MPa |
-1...10 bar: | -14.5...145 psi |
Set point SP: | -0.88...10 bar -12.8...145 psi -0.088...1 MPa |
-0.88...10 bar: | -12.8...145 psi |
Reset point rP: | -0.94...9.94 bar -13.6...144.2 psi > -0.094 MPa |
-0.94...9.94 bar: | -13.6...144.2 psi |
Analogue start point: | -1...7.26 bar -14.6...105.2 psi -0.1...0.726 MPa |
-1...7.26 bar: | -14.6...105.2 psi |
Analogue end point: | 21.8...145 psi 0.15...1 MPa |
21.8...145 psi: | 0.15...1 MPa |
In steps of: | 0.02 bar 0.29 psi 0.002 MPa |
0.02 bar: | 0.29 psi |
Factory setting: | SP1 = 36.2 psi rP1 = 33.4 psi SP2 = 108.8 psi rP2 = 105.8 psi ASP = 0.0 psi AEP = 145.0 psi |
Switch point accuracy [% of the span]: | < ± 0,4; (Turn down 1:1) |
Repeatability [% of the span]: | < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1) |
Characteristics deviation [% of the span]: | < ± 0,25 (BFSL) / < ± 0,5 (LS); (Turn down 1:1; BFSL = Best Fit Straight Line; LS = limit value setting) |
Hysteresis deviation [% of the span]: | < ± 0,1; (Turn down 1:1) |
Long-term stability [% of the span]: | < ± 0,1; (Turn down 1:1; per year) |
Temperature coefficient zero point [% of the span / 10 K]: | < ± 0,2; (-25...80 °C) |
Temperature coefficient span [% of the span / 10 K]: | < ± 0,2; (-25...80 °C) |
Response time [ms]: | < 1.5 |
Damping for the switching output dAP [s]: | 0.01...4 |
Damping for the analogue output dAA [s]: | 0.01...4 |
Max. response time analogue output [ms]: | 3 |
Parameter setting options: | hysteresis / window; normally open / normally closed; switching logic; current/voltage output; Damping; adaptation of displayed values; display can be rotated and switched off; Display unit; zero point; span |
Communication interface: | IO-Link |
Transmission type: | COM2 (38,4 kBaud) |
IO-Link revision: | 1.0 |
Ambient temperature [°C]: | -25...80 |
Storage temperature [°C]: | -40...100 |
Protection: | IP 65 |
EMC: | DIN EN 61000-6-2 DIN EN 61000-6-3 |
Shock resistance: | DIN EN 60068-2-27 50 g (11 ms) |
DIN EN 60068-2-27: | 50 g (11 ms) |
Vibration resistance: | DIN EN 60068-2-6 20 g (10...2000 Hz) |
DIN EN 60068-2-6: | 20 g (10...2000 Hz) |
MTTF [years]: | 131 |
Pressure Equipment Directive: | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
Weight [g]: | 265 |
Materials: | stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); PC; PBT; PEI; FKM; PTFE |
Materials (wetted parts): | stainless steel (1.4305 / 303); ceramics; FKM |
Min. pressure cycles: | 100 million |
Process connection: | threaded connection 1/4" NPT internal thread |
Restrictor element integrated: | no (can be retrofitted) |
Display: | Display unit 3 x LED, green switching status 2 x LED, yellow function display alphanumeric display, 4-digit measured values alphanumeric display, 4-digit |
Display unit: | 3 x LED, green |
switching status: | 2 x LED, yellow |
function display: | alphanumeric display, 4-digit |
measured values: | alphanumeric display, 4-digit |
Notes: | discontinued article |
Pack quantity: | 1 pcs. |
Connection: | Connector: 1 x M12; Contacts: gold-plated |
ECCN: | |
Country of Origin: | RO |
EAN: | |
Weight: | 0.27 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |