Description

For applications in hazardous areas. With switching output and analogue output. Clearly visible 4-digit LED display. Robust stainless steel housing for use in harsh industrial environments. Lifespan of more than 100 million pressure cycles

Technical parameters

Output signal: switching signal; analogue signal; (configurable)
Measuring range: -1...10 bar -14.5...145 psi -100...1000 kPa -0.1...1 MPa
-1...10 bar: -14.5...145 psi
Process connection: threaded connection G 1/4 internal thread
Special feature: Gold-plated contacts
Application: for industrial applications
Media: liquids and gases
Medium temperature [°C]: -20...60
Min. bursting pressure: 150 bar 2175 psi 15 MPa
150 bar: 2175 psi
Pressure rating: 75 bar 1087 psi 7.5 Mpa
75 bar: 1087 psi
Type of pressure: relative pressure
Operating voltage [V]: 18...36 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA]: < 50
Protection class: III
Reverse polarity protection: yes
Overvoltage protection: yes; (< 40 V)
Power-on delay time [s]: 0.3
Integrated watchdog: yes
Number of inputs and outputs: Number of digital outputs: 1; Number of analogue outputs: 1
Total number of outputs: 2
Output signal: switching signal; analogue signal; (configurable)
Electrical design: PNP
Number of digital outputs: 1
Output function: normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V]: 2
Permanent current rating of switching output DC [mA]: 250
Switching frequency DC [Hz]: < 170
Number of analogue outputs: 1
Analogue current output [mA]: 4...20
Max. load [Ω]: 500
Analogue voltage output [V]: 0...10
Min. load resistance [Ω]: 2000
Short-circuit protection: yes
Type of short-circuit protection: pulsed
Measuring range: -1...10 bar -14.5...145 psi -100...1000 kPa -0.1...1 MPa
-1...10 bar: -14.5...145 psi
Set point SP: -0.9...10 bar -12...145 psi -0.09...1 MPa
-0.9...10 bar: -12...145 psi
Reset point rP: -0.95...9.95 bar -13...144 psi -0.095...0.995 MPa
-0.95...9.95 bar: -13...144 psi
In steps of: 0.05 bar 1 psi 0.005 MPa
0.05 bar: 1 psi
Factory setting: SP1 = 2.50 bar rP1 = 2.30 bar
SP1 = 2.50 bar: rP1 = 2.30 bar
Switch point accuracy [% of the span]: < ± 0,5
Repeatability [% of the span]: < ± 0,1; (with temperature fluctuations < 10 K)
Characteristics deviation [% of the span]: < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting)
Hysteresis deviation [% of the span]: < ± 0,25
Long-term stability [% of the span]: < ± 0,05; (per 6 months)
Temperature coefficient zero point [% of the span / 10 K]: 0,2; (0...60 °C)
Temperature coefficient span [% of the span / 10 K]: 0,2; (0...60 °C)
Delay time programmable dS, dr [s]: 0; 0,2...50
Max. response time analogue output [ms]: 3
Parameter setting options: hysteresis / window; normally open / normally closed; switch-on/switch-off delay; Damping; Display unit; current/voltage output
Ambient temperature [°C]: -20...60
Storage temperature [°C]: -40...100
Protection: IP 65
ATEX marking: II 3D Ex tc IIIC T80°C Dc X
EMC: EN 61000-4-2 ESD 4 kV CD / 8 kV AD EN 61000-4-3 HF radiated 10 V/m EN 61000-4-4 Burst 2 kV EN 61000-4-5 Surge 0,5/1 kV EN 61000-4-6 HF conducted 10 V
EN 61000-4-2 ESD: 4 kV CD / 8 kV AD
EN 61000-4-3 HF radiated: 10 V/m
EN 61000-4-4 Burst: 2 kV
EN 61000-4-5 Surge: 0,5/1 kV
EN 61000-4-6 HF conducted: 10 V
Shock resistance: DIN IEC 68-2-27 50 g (11 ms)
DIN IEC 68-2-27: 50 g (11 ms)
Vibration resistance: DIN IEC 68-2-6 20 g (10...2000 Hz)
DIN IEC 68-2-6: 20 g (10...2000 Hz)
MTTF [years]: 213
Pressure Equipment Directive: Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Weight [g]: 302.5
Materials: stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); PC; PBT; PEI; FKM; PTFE
Materials (wetted parts): stainless steel (1.4305 / 303); ceramics; FKM
Min. pressure cycles: 100 million
Process connection: threaded connection G 1/4 internal thread
Restrictor element integrated: no (can be retrofitted)
Display: Display unit 3 x LED, green switching status LED, yellow function display alphanumeric display, 4-digit measured values alphanumeric display, 4-digit
Display unit: 3 x LED, green
switching status: LED, yellow
function display: alphanumeric display, 4-digit
measured values: alphanumeric display, 4-digit
Pack quantity: 1 pcs.
Connection: Connector: 1 x M12; Contacts: gold-plated

Logistic parameters

ECCN:
Country of Origin: RO
EAN:
Weight: 0.30 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m