PIM694
Pressure sensor with diagnostic function for pumps. PIM010-REA01-KFPKG/US/ /P
Two functions in one unit: Pump monitoring and pressure detection. Reliable diagnosis of disturbances in the suction area and detection of cavitation. Detection of outgassing liquids or trapped air in the pump. Independent system-pressure monitoring with second switching output. Pump control via analogue output
Output signal: | switching signal; analogue signal; (configurable) |
Measuring range: | -1...10 bar -14.5...145 psi -0.1...1 MPa |
-1...10 bar: | -14.5...145 psi |
Process connection: | threaded connection G 1 external thread sealing cone |
Special feature: | Gold-plated contacts |
Application: | food and beverage industry |
Installation: | freely rotatable housing 350° |
Media: | viscous media and liquids with suspended particles; liquids and gases |
Medium temperature [°C]: | -25...125; (145 max. 1h) |
Min. bursting pressure: | 150 bar 2175 psi 15 MPa |
150 bar: | 2175 psi |
Pressure rating: | 50 bar 725 psi 5 Mpa |
50 bar: | 725 psi |
Type of pressure: | relative pressure; vacuum |
No dead space: | yes |
Operating voltage [V]: | 18...32 DC |
Current consumption [mA]: | < 50 |
Min. insulation resistance [MΩ]: | 100; (500 V DC) |
Protection class: | III |
Reverse polarity protection: | yes |
Power-on delay time [s]: | 0.2 |
Integrated watchdog: | yes |
Number of inputs and outputs: | Number of digital outputs: 2; Number of analogue outputs: 1 |
Total number of outputs: | 2 |
Output signal: | switching signal; analogue signal; (configurable) |
Electrical design: | PNP |
Number of digital outputs: | 2 |
Output function: | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V]: | 2 |
Permanent current rating of switching output DC [mA]: | 250 |
Switching frequency DC [Hz]: | 350 |
Notes on switching frequency: | OUT2 |
Number of analogue outputs: | 1 |
Analogue current output [mA]: | 4...20, invertible; (scalable) |
Max. load [Ω]: | (Ub - 10 V) / 20 mA |
Short-circuit protection: | yes |
Type of short-circuit protection: | pulsed |
Overload protection: | yes |
Measuring range: | -1...10 bar -14.5...145 psi -0.1...1 MPa |
-1...10 bar: | -14.5...145 psi |
Set point SP: | -0.98...10 bar -14.2...145 psi -0.098...1 MPa |
-0.98...10 bar: | -14.2...145 psi |
Reset point rP: | -1...9.98 bar -14.5...144.7 psi -0.1...0.998 MPa |
-1...9.98 bar: | -14.5...144.7 psi |
Analogue start point: | -1...7.25 bar -14.5...105.1 psi -0.1...0.725 MPa |
-1...7.25 bar: | -14.5...105.1 psi |
Analogue end point: | 1.5...10 bar 21.8...145 psi 0.15...1 MPa |
1.5...10 bar: | 21.8...145 psi |
In steps of: | 0.01 bar 0.1 psi 0.001 MPa |
0.01 bar: | 0.1 psi |
Factory setting: | OU1 = Fnc OU2 = I ASP = 0.00 bar AEP = 10.00 bar |
Switch point accuracy [% of the span]: | < ± 0,2; (Turn down 1:1) |
Repeatability [% of the span]: | < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1) |
Characteristics deviation [% of the span]: | < ± 0,2; (Turn down 1:1 linearity, incl. hysteresis and repeatability limit value setting to DIN 16086) |
Linearity deviation [% of the span]: | < ± 0,15; (Turn down 1:1) |
Hysteresis deviation [% of the span]: | < ± 0,15; (Turn down 1:1) |
Long-term stability [% of the span]: | < ± 0,1; (Turn down 1:1; per year) |
Temperature coefficient zero point [% of the span / 10 K]: | < ± 0,15; (0...70 °C) |
Temperature coefficient span [% of the span / 10 K]: | < ± 0,1; (0...70 °C) |
Response time [ms]: | < 2.5 |
Damping for the switching output dAP [s]: | 0...10 |
Damping for the analogue output dAA [s]: | 0...10 |
Step response time analogue output [ms]: | 0.2 |
Parameter setting options: | zero point; span |
Ambient temperature [°C]: | -25...80 |
Storage temperature [°C]: | -40...100 |
Protection: | IP 67; IP 69K |
EMC: | EN 61000-4-2 ESD 4 kV CD / 8 kV AD EN 61000-4-3 HF radiated 10 V/m EN 61000-4-4 Burst 2 kV EN 61000-4-5 Surge 0,5/1 kV EN 61000-4-6 HF conducted 10 V |
EN 61000-4-2 ESD: | 4 kV CD / 8 kV AD |
EN 61000-4-3 HF radiated: | 10 V/m |
EN 61000-4-4 Burst: | 2 kV |
EN 61000-4-5 Surge: | 0,5/1 kV |
EN 61000-4-6 HF conducted: | 10 V |
Shock resistance: | DIN IEC 68-2-27 50 g (11 ms) |
DIN IEC 68-2-27: | 50 g (11 ms) |
Vibration resistance: | DIN IEC 68-2-6 20 g (10...2000 Hz) |
DIN IEC 68-2-6: | 20 g (10...2000 Hz) |
MTTF [years]: | 188 |
Weight [g]: | 451.2 |
Materials: | stainless steel (1.4404 / 316L); PC; PBT; PEI; FKM; PTFE |
Materials (wetted parts): | ceramics (99.9 % Al2O3); stainless steel (1.4435 / 316L); surface characteristics: Ra < 0,4 / Rz 4; PTFE |
Min. pressure cycles: | 100 million |
Process connection: | threaded connection G 1 external thread sealing cone |
Display: | Display unit 4 x LED, green switching status 2 x LED, yellow function display alphanumeric display, 4-digit measured values alphanumeric display, 4-digit |
Display unit: | 4 x LED, green |
switching status: | 2 x LED, yellow |
function display: | alphanumeric display, 4-digit |
measured values: | alphanumeric display, 4-digit |
Remarks: | pump diagnosis for pumps with constant rotational speed (+/- 10 % deviation of the taught rotational speed) speed range 40...3000 U/min minimum pressure for pump diagnosis 0,5 bar The 3-A qualification is only valid if adapters with 3-A qualification are used for installation. |
Pack quantity: | 1 pcs. |
Connection: | Connector: 1 x M12; Contacts: gold-plated |
ECCN: | |
Country of Origin: | DE |
EAN: | |
Weight: | 0.45 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |