Ifm PIM094

Pressure sensor with diagnostic function for pumps. PIM010-RES30-KFPKG/US/ /P

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

Two functions in one unit: Pump monitoring and pressure detection. Reliable diagnosis of disturbances in the suction area and detection of cavitation. Detection of outgassing liquids or trapped air in the pump. Independent system-pressure monitoring with second switching output. Pump control via analogue output

Technical parameters

Output signal: switching signal; analogue signal; (configurable)
Measuring range: -1...10 bar -14.5...145 psi -0.1...1 MPa
-1...10 bar: -14.5...145 psi
Process connection: threaded connection Aseptoflex external thread Aseptoflex
Special feature: Gold-plated contacts
Application: food and beverage industry
Installation: freely rotatable housing 350°
Media: viscous media and liquids with suspended particles; liquids and gases
Medium temperature [°C]: -25...125; (145 max. 1h)
Min. bursting pressure: 150 bar 2175 psi 15 MPa
150 bar: 2175 psi
Pressure rating: 50 bar 725 psi 5 Mpa
50 bar: 725 psi
Type of pressure: relative pressure
No dead space: yes
Operating voltage [V]: 18...32 DC
Current consumption [mA]: < 50
Min. insulation resistance [MΩ]: 100; (500 V DC)
Protection class: III
Reverse polarity protection: yes
Power-on delay time [s]: 0.2
Integrated watchdog: yes
Number of inputs and outputs: Number of digital outputs: 2; Number of analogue outputs: 1
Total number of outputs: 2
Output signal: switching signal; analogue signal; (configurable)
Electrical design: PNP
Number of digital outputs: 2
Output function: normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V]: 2
Permanent current rating of switching output DC [mA]: 250
Switching frequency DC [Hz]: 350
Notes on switching frequency: OUT2
Number of analogue outputs: 1
Analogue current output [mA]: 4...20, invertible; (scalable)
Max. load [Ω]: (Ub - 10 V) / 20 mA
Short-circuit protection: yes
Type of short-circuit protection: pulsed
Overload protection: yes
Measuring range: -1...10 bar -14.5...145 psi -0.1...1 MPa
-1...10 bar: -14.5...145 psi
Set point SP: -0.98...10 bar -14.2...145 psi -0.098...1 MPa
-0.98...10 bar: -14.2...145 psi
Reset point rP: -1...9.98 bar -14.5...144.7 psi -0.1...0.998 MPa
-1...9.98 bar: -14.5...144.7 psi
Analogue start point: -1...7.25 bar -14.5...105.1 psi -0.1...0.725 MPa
-1...7.25 bar: -14.5...105.1 psi
Analogue end point: 1.5...10 bar 21.8...145 psi 0.15...1 MPa
1.5...10 bar: 21.8...145 psi
In steps of: 0.01 bar 0.1 psi 0.001 MPa
0.01 bar: 0.1 psi
Factory setting: OU1 = Fnc OU2 = I ASP = 0.00 bar AEP = 10.00 bar
Switch point accuracy [% of the span]: < ± 0,2; (Turn down 1:1)
Repeatability [% of the span]: < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1)
Characteristics deviation [% of the span]: < ± 0,2; (Turn down 1:1 linearity, incl. hysteresis and repeatability limit value setting to DIN 16086)
Linearity deviation [% of the span]: < ± 0,15; (Turn down 1:1)
Hysteresis deviation [% of the span]: < ± 0,15; (Turn down 1:1)
Long-term stability [% of the span]: < ± 0,1; (Turn down 1:1; per year)
Temperature coefficient zero point [% of the span / 10 K]: < ± 0,15; (0...70 °C)
Temperature coefficient span [% of the span / 10 K]: < ± 0,1; (0...70 °C)
Response time [ms]: < 2.5
Damping for the switching output dAP [s]: 0...10
Damping for the analogue output dAA [s]: 0...10
Step response time analogue output [ms]: 0.2
Parameter setting options: zero point; span
Ambient temperature [°C]: -25...80
Storage temperature [°C]: -40...100
Protection: IP 67; IP 69K
EMC: EN 61000-4-2 ESD 4 kV CD / 8 kV AD EN 61000-4-3 HF radiated 10 V/m EN 61000-4-4 Burst 2 kV EN 61000-4-5 Surge 0,5/1 kV EN 61000-4-6 HF conducted 10 V
EN 61000-4-2 ESD: 4 kV CD / 8 kV AD
EN 61000-4-3 HF radiated: 10 V/m
EN 61000-4-4 Burst: 2 kV
EN 61000-4-5 Surge: 0,5/1 kV
EN 61000-4-6 HF conducted: 10 V
Shock resistance: DIN IEC 68-2-27 50 g (11 ms)
DIN IEC 68-2-27: 50 g (11 ms)
Vibration resistance: DIN IEC 68-2-6 20 g (10...2000 Hz)
DIN IEC 68-2-6: 20 g (10...2000 Hz)
MTTF [years]: 188
Weight [g]: 414.5
Materials: stainless steel (1.4404 / 316L); PC; PBT; PEI; FKM; PTFE
Materials (wetted parts): ceramics (99.9 % Al2O3); stainless steel (1.4435 / 316L); surface characteristics: Ra < 0,4 / Rz 4; PTFE
Min. pressure cycles: 100 million
Process connection: threaded connection Aseptoflex external thread Aseptoflex
Display: Display unit 4 x LED, green switching status 2 x LED, yellow function display alphanumeric display, 4-digit measured values alphanumeric display, 4-digit
Display unit: 4 x LED, green
switching status: 2 x LED, yellow
function display: alphanumeric display, 4-digit
measured values: alphanumeric display, 4-digit
Remarks: pump diagnosis for pumps with constant rotational speed (+/- 10 % deviation of the taught rotational speed) speed range 40...3000 U/min minimum pressure for pump diagnosis 0,5 bar The 3-A qualification is only valid if adapters with 3-A qualification are used for installation.
Pack quantity: 1 pcs.
Connection: Connector: 1 x M12; Contacts: gold-plated

Logistic parameters

ECCN:
Country of Origin: DE
EAN:
Weight: 0.41 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m