PG2899
Flush pressure sensor with analogue display. PG-1-1BREA01-MFRKG/US/ /P
Analogue display, pressure switch and transmitter in one unit. Excellent readability also over a long distance. Rotatable display with LED bar graph for switch point indication. Hygienic, robust stainless steel housing for the requirements of the food and beverage industry. Flush process connection for use in CIP and SIP processes
Output signal: | switching signal; analogue signal; (configurable) |
Measuring range: | -1...1 bar -1000...1000 mbar -14.5...14.5 psi |
-1...1 bar: | -1000...1000 mbar |
Process connection: | threaded connection G 1 external thread sealing cone |
Special feature: | Gold-plated contacts |
Application: | food and beverage industry; Safety manometer (S) based on DIN EN 837-1 |
Media: | viscous media and liquids with suspended particles; liquids and gases |
Medium temperature [°C]: | -25...125; (145 max. 1h) |
Min. bursting pressure: | 30 bar 435 psi |
30 bar: | 435 psi |
Pressure rating: | 10 bar 145 psi |
10 bar: | 145 psi |
Type of pressure: | relative pressure; vacuum |
MAWP (for applications according to CRN) [bar]: | 10 |
Operating voltage [V]: | 18...32 DC |
Current consumption [mA]: | < 70; (24 V) |
Min. insulation resistance [MΩ]: | 100; (500 V DC) |
Protection class: | III |
Reverse polarity protection: | yes |
Power-on delay time [s]: | 6 |
Integrated watchdog: | yes |
Number of inputs and outputs: | Number of digital outputs: 1; Number of analogue outputs: 1 |
Total number of outputs: | 2 |
Output signal: | switching signal; analogue signal; (configurable) |
Electrical design: | PNP/NPN |
Number of digital outputs: | 1 |
Output function: | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V]: | 2 |
Permanent current rating of switching output DC [mA]: | 250 |
Switching frequency DC [Hz]: | 50 |
Number of analogue outputs: | 1 |
Analogue current output [mA]: | 4...20, invertible; (scalable) |
Max. load [Ω]: | (Ub - 10 V) / 20 mA |
Short-circuit protection: | yes |
Type of short-circuit protection: | pulsed |
Overload protection: | yes |
Measuring range: | -1...1 bar -1000...1000 mbar -14.5...14.5 psi |
-1...1 bar: | -1000...1000 mbar |
Set point SP: | -0.998...1.6 bar -14.48...23.2 psi |
-0.998...1.6 bar: | -14.48...23.2 psi |
Reset point rP: | -1...1.598 bar -14.5...23.18 psi |
-1...1.598 bar: | -14.5...23.18 psi |
Analogue start point: | -1...1.1 bar -14.5...15.96 psi |
-1...1.1 bar: | -14.5...15.96 psi |
Analogue end point: | -0.5...1.6 bar -7.26...23.2 psi |
-0.5...1.6 bar: | -7.26...23.2 psi |
In steps of: | 0.001 bar 0.02 psi |
0.001 bar: | 0.02 psi |
Switch point accuracy [% of the span]: | < ± 0,2; (Turn down 1:1) |
Repeatability [% of the span]: | < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1) |
Characteristics deviation [% of the span]: | < ± 0,2; (Turn down 1:1 linearity, incl. hysteresis and repeatability limit value setting to DIN 16086) |
Linearity deviation [% of the span]: | < ± 0,15; (Turn down 1:1) |
Hysteresis deviation [% of the span]: | < ± 0,15; (Turn down 1:1) |
Long-term stability [% of the span]: | < ± 0,1; (Turn down 1:1; per year) |
Temperature coefficient zero point [% of the span / 10 K]: | < ± 0,05; (0...70 °C) |
Temperature coefficient span [% of the span / 10 K]: | < ± 0,15; (0...70 °C) |
Response time [ms]: | < 10 |
Damping for the switching output dAP [s]: | 0.01...30 |
Damping for the analogue output dAA [s]: | 0.01...30 |
Step response time analogue output [ms]: | 25 |
Ambient temperature [°C]: | -25...80 |
Storage temperature [°C]: | -40...100 |
Protection: | IP 67; IP 69K |
EMC: | EN 61000-4-2 ESD 4 kV CD / 8 kV AD EN 61000-4-3 HF radiated 10 V/m EN 61000-4-4 Burst 2 kV EN 61000-4-5 Surge 0,5/1 kV EN 61000-4-6 HF conducted 10 V |
EN 61000-4-2 ESD: | 4 kV CD / 8 kV AD |
EN 61000-4-3 HF radiated: | 10 V/m |
EN 61000-4-4 Burst: | 2 kV |
EN 61000-4-5 Surge: | 0,5/1 kV |
EN 61000-4-6 HF conducted: | 10 V |
Shock resistance: | DIN IEC 68-2-27 50 g (11 ms) |
DIN IEC 68-2-27: | 50 g (11 ms) |
Vibration resistance: | DIN IEC 68-2-6 20 g (10...2000 Hz) |
DIN IEC 68-2-6: | 20 g (10...2000 Hz) |
MTTF [years]: | 100 |
Note on approval: | factory certificate available as download at www.factory-certificate.ifm |
Weight [g]: | 563 |
Materials: | stainless steel (1.4404 / 316L); PA; FKM; PTFE; viewing glass: laminated safety glass 4 mm |
Materials (wetted parts): | ceramics (99.9 % Al2O3); stainless steel (1.4435 / 316L); surface characteristics: Ra < 0,4 / Rz 4; PTFE |
Min. pressure cycles: | 100 million |
Process connection: | threaded connection G 1 external thread sealing cone |
Display: | Display unit 2 x LED, green switching status LED, yellow switch points LED ring, red function display alphanumeric display, red 4-digit measured values analogue display, 0...350° rotatable, pointer not visible when unit disconnected measured values alphanumeric display, red 4-digit |
Display unit: | 2 x LED, green |
switching status: | LED, yellow |
switch points: | LED ring, red |
function display: | alphanumeric display, red 4-digit |
measured values: | analogue display, 0...350° rotatable, pointer not visible when unit disconnected |
measured values: | alphanumeric display, red 4-digit |
With scale: | yes |
Extended display range (max.): | 1.6 bar 23.2 psi |
1.6 bar: | 23.2 psi |
Remarks: | Attention: The unit must only be installed in a process connection for G1 sealing cone. The G1A sealing cone of the unit is only suited for adapters with metal end stop. characteristics deviation in the extended display range: 1.5 % of the span switch point accuracy in the extended display range: 1.5 % of the span |
Pack quantity: | 1 pcs. |
Connection: | Connector: 1 x M12; Contacts: gold-plated |
ECCN: | |
Country of Origin: | DE |
EAN: | |
Weight: | 0.56 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |