PG2454
Pressure sensor with analogue display. PG-010-REB12-MFRKG/US/ /P
Analogue display, pressure switch and transmitter in one unit. Excellent readability also over a long distance. Rotatable display with LED bar graph for switch point indication. Programmable switching output and scalable analogue output. Robust stainless steel housing for use in harsh industrial environments
| Output signal: | switching signal; analogue signal; (configurable) |
| Measuring range: | -1...10 bar -14.4...145 psi |
| -1...10 bar: | -14.4...145 psi |
| Process connection: | threaded connection G 1/2 external thread |
| Special feature: | Gold-plated contacts |
| Application: | for industrial applications; Safety manometer (S) based on DIN EN 837-1 |
| Media: | liquids and gases |
| Medium temperature [°C]: | -25...80 |
| Min. bursting pressure: | 150 bar 2175 psi |
| 150 bar: | 2175 psi |
| Pressure rating: | 50 bar 725 psi |
| 50 bar: | 725 psi |
| Type of pressure: | relative pressure; vacuum |
| MAWP (for applications according to CRN): | 38 bar 551 psi |
| 38 bar: | 551 psi |
| Operating voltage [V]: | 18...32 DC |
| Current consumption [mA]: | < 70; (24 V) |
| Min. insulation resistance [MΩ]: | 100; (500 V DC) |
| Protection class: | III |
| Reverse polarity protection: | yes |
| Power-on delay time [s]: | 6 |
| Integrated watchdog: | yes |
| Number of inputs and outputs: | Number of digital outputs: 1; Number of analogue outputs: 1 |
| Total number of outputs: | 2 |
| Output signal: | switching signal; analogue signal; (configurable) |
| Electrical design: | PNP/NPN |
| Number of digital outputs: | 1 |
| Output function: | normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC [V]: | 2 |
| Permanent current rating of switching output DC [mA]: | 250 |
| Switching frequency DC [Hz]: | 75 |
| Number of analogue outputs: | 1 |
| Analogue current output [mA]: | 4...20, invertible; (scalable) |
| Max. load [Ω]: | (Ub - 10 V) / 20 mA |
| Short-circuit protection: | yes |
| Type of short-circuit protection: | pulsed |
| Overload protection: | yes |
| Measuring range: | -1...10 bar -14.4...145 psi |
| -1...10 bar: | -14.4...145 psi |
| Set point SP: | -0.96...16 bar -14...232 psi |
| -0.96...16 bar: | -14...232 psi |
| Reset point rP: | -1...15.96 bar -14.4...231.6 psi |
| -1...15.96 bar: | -14.4...231.6 psi |
| Analogue start point: | -1...13.5 bar -14.4...195.8 psi |
| -1...13.5 bar: | -14.4...195.8 psi |
| Analogue end point: | 1.5...16 bar 21.8...232 psi |
| 1.5...16 bar: | 21.8...232 psi |
| In steps of: | 0.02 bar 0.2 psi |
| 0.02 bar: | 0.2 psi |
| Switch point accuracy [% of the span]: | < ± 0,5; (Turn down 1:1) |
| Repeatability [% of the span]: | < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1) |
| Characteristics deviation [% of the span]: | < ± 0,25 (BFSL) / < ± 0,5 (LS); (Turn down 1:1; BFSL = Best Fit Straight Line) |
| Hysteresis deviation [% of the span]: | < ± 0,25; (Turn down 1:1) |
| Long-term stability [% of the span]: | < ± 0,1; (Turn down 1:1; per 6 months) |
| Temperature coefficient zero point [% of the span / 10 K]: | < ± 0,2; (0...70 °C) |
| Temperature coefficient span [% of the span / 10 K]: | < ± 0,2; (0...70 °C) |
| Response time [ms]: | < 9 |
| Damping for the switching output dAP [s]: | 0.01...30 |
| Damping for the analogue output dAA [s]: | 0.01...30 |
| Step response time analogue output [ms]: | 28 |
| Ambient temperature [°C]: | -20...80 |
| Storage temperature [°C]: | -40...100 |
| Protection: | IP 67; IP 69K |
| EMC: | DIN EN 61000-6-2 DIN EN 61000-6-3 |
| Shock resistance: | DIN EN 60068-2-27 50 g (11 ms) |
| DIN EN 60068-2-27: | 50 g (11 ms) |
| Vibration resistance: | DIN EN 60068-2-6 20 g (10...2000 Hz) |
| DIN EN 60068-2-6: | 20 g (10...2000 Hz) |
| MTTF [years]: | 103 |
| Pressure Equipment Directive: | Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request |
| Weight [g]: | 608 |
| Materials: | stainless steel (1.4404 / 316L); PA; FKM; PTFE; viewing glass: laminated safety glass 4 mm |
| Materials (wetted parts): | Al2O3 (ceramics); FKM; stainless steel (1.4404 / 316L) |
| Min. pressure cycles: | 100 million |
| Process connection: | threaded connection G 1/2 external thread |
| Restrictor element integrated: | no (can be retrofitted) |
| Display: | Display unit 2 x LED, green switching status LED, yellow switch points LED ring, red function display alphanumeric display, red 4-digit measured values analogue display, 0...350° rotatable, pointer not visible when unit disconnected measured values alphanumeric display, red 4-digit |
| Display unit: | 2 x LED, green |
| switching status: | LED, yellow |
| switch points: | LED ring, red |
| function display: | alphanumeric display, red 4-digit |
| measured values: | analogue display, 0...350° rotatable, pointer not visible when unit disconnected |
| measured values: | alphanumeric display, red 4-digit |
| With scale: | yes |
| Extended display range (max.): | 16 bar 232 psi |
| 16 bar: | 232 psi |
| Remarks: | switch point accuracy in the extended display range: 1.5 % of the span |
| Pack quantity: | 1 pcs. |
| Connection: | Connector: 1 x M12; Contacts: gold-plated |
| ECCN: | |
| Country of Origin: | DE |
| EAN: | |
| Weight: | 0.61 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |