Ifm PE3002

Pressure sensor with display. PE-100-SDR14-MFPKG/US/ /E

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

Special seal for use in cleaning processes. With programmable switching output and analogue output. With long-term stability thanks to high overload protection. Clearly visible 4-digit LED display. High shock and vibration resistance

Technical parameters

Output signal: switching signal; analogue signal; (configurable)
Measuring range: 0...100 bar 0...1450 psi 0...10 MPa
0...100 bar: 0...1450 psi
Process connection: threaded connection G 1/4 internal thread
Special feature: Gold-plated contacts
Application: for industrial applications
Media: liquids and gases
Conditionally suitable for: use in gases at pressures > 25 bar only on request
Cannot be used for: oils
Medium temperature [°C]: -25...80
Min. bursting pressure: 650 bar 9400 psi 65 MPa
650 bar: 9400 psi
Pressure rating: 300 bar 4350 psi 30 Mpa
300 bar: 4350 psi
Type of pressure: relative pressure
Operating voltage [V]: 18...36 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA]: < 50
Min. insulation resistance [MΩ]: 100; (500 V DC)
Protection class: III
Reverse polarity protection: yes
Overvoltage protection: yes; (< 40 V)
Power-on delay time [s]: 0.3
Integrated watchdog: yes
Number of inputs and outputs: Number of digital outputs: 1; Number of analogue outputs: 1
Total number of outputs: 2
Output signal: switching signal; analogue signal; (configurable)
Electrical design: PNP
Number of digital outputs: 1
Output function: normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V]: 2
Permanent current rating of switching output DC [mA]: 250
Switching frequency DC [Hz]: < 170
Number of analogue outputs: 1
Analogue current output [mA]: 4...20
Max. load [Ω]: 500
Analogue voltage output [V]: 0...10
Min. load resistance [Ω]: 2000
Short-circuit protection: yes
Type of short-circuit protection: pulsed
Measuring range: 0...100 bar 0...1450 psi 0...10 MPa
0...100 bar: 0...1450 psi
Set point SP: 1...100 bar 20...1450 psi 0.1...10 MPa
1...100 bar: 20...1450 psi
Reset point rP: 0.5...99.5 bar 10...1440 psi 0.05...9.95 MPa
0.5...99.5 bar: 10...1440 psi
In steps of: 0.5 bar 10 psi 0.05 MPa
0.5 bar: 10 psi
Factory setting: SP1 = 25.0 bar rP1 = 23.0 bar
Switch point accuracy [% of the span]: < ± 0,5
Repeatability [% of the span]: < ± 0,1; (with temperature fluctuations < 10 K)
Characteristics deviation [% of the span]: < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting)
Hysteresis deviation [% of the span]: < ± 0,25
Long-term stability [% of the span]: < ± 0,05; (per 6 months)
Temperature coefficient zero point [% of the span / 10 K]: 0,2; (-20...80 °C)
Temperature coefficient span [% of the span / 10 K]: 0,2; (-20...80 °C)
Delay time programmable dS, dr [s]: 0; 0,2...50
Max. response time analogue output [ms]: 3
Parameter setting options: hysteresis / window; normally open / normally closed; switch-on/switch-off delay; Damping; Display unit; current/voltage output
Ambient temperature [°C]: -20...80
Storage temperature [°C]: -40...100
Protection: IP 67
EMC: EN 61000-4-2 ESD 4 kV CD / 8 kV AD EN 61000-4-3 HF radiated 10 V/m EN 61000-4-4 Burst 2 kV EN 61000-4-5 Surge 0,5/1 kV EN 61000-4-6 HF conducted 10 V
EN 61000-4-2 ESD: 4 kV CD / 8 kV AD
EN 61000-4-3 HF radiated: 10 V/m
EN 61000-4-4 Burst: 2 kV
EN 61000-4-5 Surge: 0,5/1 kV
EN 61000-4-6 HF conducted: 10 V
Shock resistance: DIN IEC 68-2-27 50 g (11 ms)
DIN IEC 68-2-27: 50 g (11 ms)
Vibration resistance: DIN IEC 68-2-6 20 g (10...2000 Hz)
DIN IEC 68-2-6: 20 g (10...2000 Hz)
MTTF [years]: 213
Pressure Equipment Directive: Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Weight [g]: 262
Materials: stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L); PC; PBT; PEI; FKM
Materials (wetted parts): stainless steel (1.4404 / 316L); ceramics; sealing of the measuring cell: EPDM
Min. pressure cycles: 100 million
Process connection: threaded connection G 1/4 internal thread
Display: Display unit 3 x LED, green switching status LED, yellow function display alphanumeric display, 4-digit measured values alphanumeric display, 4-digit
Display unit: 3 x LED, green
switching status: LED, yellow
function display: alphanumeric display, 4-digit
measured values: alphanumeric display, 4-digit
Pack quantity: 1 pcs.
Connection: Connector: 1 x M12; Contacts: gold-plated

Logistic parameters

ECCN:
Country of Origin: DE
EAN:
Weight: 0.26 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m