NT5001
Inductive NAMUR sensor. ITA2001-N/1D/1G
For applications in hazardous areas. For connection to intrinsically safe circuits. Particularly short housing for use where space is restricted. Very high switching frequency. Robust metal housing for use in harsh industrial environments
Electrical design: | NAMUR |
Output function: | normally closed |
Sensing range [mm]: | 1 |
Housing: | cylindrical |
Dimensions [mm]: | Ø 6.5 / L = 30 |
Connection to switching amplifiers: | yes |
Switching amplifiers: | connection to certified intrinsically safe circuits with the max. values: U = 15 V / I = 50 mA / P = 120 mW |
Nominal voltage DC [V]: | 8.2; (1kΩ) |
Supply voltage DC [V]: | 7.5...30; (when used outside the hazardous area) |
Current consumption [mA]: | < 1; (disabled; conductive: > 2,1) |
Protection class: | III |
Electrical design: | NAMUR |
Output function: | normally closed |
Permanent current rating of switching output DC [mA]: | 30; (when used outside the hazardous area) |
Switching frequency DC [Hz]: | 2000 |
Sensing range [mm]: | 1 |
Real sensing range Sr [mm]: | 1 ± 10 % |
Correction factor: | steel: 1 / stainless steel: 0.7 / brass: 0.5 / aluminium: 0.4 / copper: 0.3 |
Hysteresis [% of Sr]: | 1...15 |
Switch point drift [% of Sr]: | -10...10 |
Ambient temperature [°C]: | -20...80 |
Protection: | IP 67 |
Approval: | PTB 01 ATEX 2191; BVS 04 ATEX E153; IECEx BVS 06.0003 |
ATEX marking: | II 1G Ex ia IIC T6 Ga Ta: -20...70° C |
EMC: | EN 60947-5-6 |
Shock/vibration resistance: | 30 g (11 ms) / 10-55 Hz (1 mm) |
MTTF [years]: | 4816 |
Max. internal capacitance [nF]: | 80 |
Max. internal inductance [µH]: | 70 |
Weight [K40]: | 90.5 |
Housing: | cylindrical |
Mounting: | flush mountable |
Dimensions [mm]: | Ø 6.5 / L = 30 |
Materials: | brass special coating; sensing face: PBT |
Pack quantity: | 1 pcs. |
Connection: | Cable: 2 m, PVC; 2 x 0.14 mm² |
ECCN: | |
Country of Origin: | DE |
EAN: | |
Weight: | 0.09 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |