NS5003
Inductive NAMUR sensor. IS-2002-N/1D/1G/2G
For applications in hazardous areas. For connection to intrinsically safe circuits. Particularly space-saving rectangular housing. For use where space is restricted. Very high switching frequency
Electrical design: | NAMUR |
Output function: | normally closed |
Sensing range [mm]: | 2 |
Housing: | rectangular |
Dimensions [mm]: | 28 x 10 x 16 |
Connection to switching amplifiers: | yes |
Switching amplifiers: | connection to certified intrinsically safe circuits with the max. values: U = 15 V / I = 50 mA / P = 120 mW |
Nominal voltage DC [V]: | 8.2; (1kΩ) |
Supply voltage DC [V]: | 7.5...30; (when used outside the hazardous area) |
Current consumption [mA]: | < 1; (disabled; conductive: > 2,1) |
Protection class: | III |
Electrical design: | NAMUR |
Output function: | normally closed |
Permanent current rating of switching output DC [mA]: | 30; (when used outside the hazardous area) |
Switching frequency DC [Hz]: | 800 |
Sensing range [mm]: | 2 |
Real sensing range Sr [mm]: | 2 ± 10 % |
Correction factor: | steel: 1 / stainless steel: 0.7 / brass: 0.5 / aluminium: 0.4 / copper: 0.3 |
Hysteresis [% of Sr]: | 1...15 |
Switch point drift [% of Sr]: | -10...10 |
Ambient temperature [°C]: | -20...70 |
Protection: | IP 67 |
Approval: | PTB 02 ATEX 2217; BVS 04 ATEX E153; IECEx BVS 06.0003 |
ATEX marking: | II 1G Ex ia IIB T6 Ga Ta: -20...70° C |
EMC: | EN 60947-5-6 |
Shock/vibration resistance: | 30 g (11 ms) / 10-55 Hz (1 mm) |
MTTF [years]: | 4494 |
Max. internal capacitance [nF]: | 80 |
Max. internal inductance [µH]: | 110 |
Weight [g]: | 79.5 |
Housing: | rectangular |
Mounting: | flush mountable |
Dimensions [mm]: | 28 x 10 x 16 |
Materials: | PBT |
Display: | switching status 1 x LED, red |
switching status: | 1 x LED, red |
Pack quantity: | 1 pcs. |
Connection: | Cable: 2 m, PVC; 2 x 0.14 mm² |
ECCN: | |
Country of Origin: | DE |
EAN: | |
Weight: | 0.08 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |