NN5020
Inductive NAMUR sensor. IN-2004-N/10M/1D/1G/2G
For use where space is restricted. Particularly space-saving rectangular housing. For applications in hazardous areas. Very high switching frequency. For connection to intrinsically safe circuits
| Electrical design: | NAMUR |
| Output function: | normally closed |
| Sensing range [mm]: | 4 |
| Housing: | rectangular |
| Dimensions [mm]: | 40 x 12 x 26 |
| Connection to switching amplifiers: | yes |
| Switching amplifiers: | connection to certified intrinsically safe circuits with the max. values: U = 15 V / I = 50 mA / P = 120 mW |
| Nominal voltage DC [V]: | 8.2; (1kΩ) |
| Supply voltage DC [V]: | 7.5...30; (when used outside the hazardous area) |
| Current consumption [mA]: | < 1; (disabled; conductive: > 2,1) |
| Protection class: | II |
| Electrical design: | NAMUR |
| Output function: | normally closed |
| Permanent current rating of switching output DC [mA]: | 30; (when used outside the hazardous area) |
| Switching frequency DC [Hz]: | 400 |
| Sensing range [mm]: | 4 |
| Real sensing range Sr [mm]: | 4 ± 10 % |
| Correction factor: | steel: 1 / stainless steel: 0.7 / brass: 0.5 / aluminium: 0.4 / copper: 0.3 |
| Hysteresis [% of Sr]: | 1...15 |
| Switch point drift [% of Sr]: | -10...10 |
| Ambient temperature [°C]: | -20...80 |
| Protection: | IP 67 |
| Approval: | PTB 01 ATEX 2191; BVS 04 ATEX E153; IECEx BVS 06.0003 |
| ATEX marking: | II 1G Ex ia IIB T6 Ga |
| EMC: | EN 60947-5-6 |
| Shock/vibration resistance: | 30 g (11 ms) / 10-55 Hz (1 mm) |
| MTTF [years]: | 4899 |
| Max. internal capacitance [nF]: | 112 |
| Max. internal inductance [µH]: | 143 |
| Weight [g]: | 447 |
| Housing: | rectangular |
| Mounting: | non-flush mountable |
| Dimensions [mm]: | 40 x 12 x 26 |
| Materials: | PBT |
| Pack quantity: | 1 pcs. |
| Connection: | Cable: 10 m, PVC; 2 x 0.5 mm² |
| ECCN: | |
| Country of Origin: | DE |
| EAN: | |
| Weight: | 0.45 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |