N0532A
Switching amplifiers for Namur sensors. NV1223/24VDC/OK/1D/1G
For the operation of intrinsically safe sensors in hazardous areas. Reliable short-circuit and wire-break monitoring. Easy programming of the output function. LED display to check operation, switching status and function. Quick and easy mounting on DIN rail
Application: | short-circuit monitoring; Wire monitoring |
Operating voltage tolerance [%]: | -15...25 |
Operating voltage [V]: | 24 DC |
Current consumption [mA]: | < 50 |
Number of channels: | 2 |
Electrical design: | opto coupler; (bipolar; Voltage: max. 40 V DC) |
Max. voltage drop switching output DC [V]: | 3 |
Max. current load per output [mA]: | 100 |
Switching frequency DC [Hz]: | 5000 |
Short-circuit proof: | yes |
Ambient temperature [°C]: | -20...60 |
Protection: | IP 20 |
Approval: | PTB 02 ATEX 2037; TIIS TC16049; IECEx PTB 06.0038 |
ATEX marking: | II (1) G [Ex ia] IIC |
EMC: | EN 50081-2 (1993) EN 61326-1 (2006) |
EN 50081-2: | (1993) |
EN 61326-1: | (2006) |
MTTF [years]: | 426 |
Weight [g]: | 170 |
Display: | switching status 2 x LED, yellow operation LED, green function 2 x LED, red |
switching status: | 2 x LED, yellow |
operation: | LED, green |
function: | 2 x LED, red |
Remarks: | Caution The control monitor must be mounted outside the hazardous area. Free terminals must not be used. |
Pack quantity: | 1 pcs. |
Connection: | terminals: ...2.5 mm² |
in protection rating intrinsic safety: | [EEx ia] IIC |
Voltage [V]: | 10.5 |
Current [mA]: | 13 |
Power [mW]: | 34 |
External inductance [mH]: | 200 |
External capacitance [µF]: | 2.4 |
ECCN: | |
Country of Origin: | SG |
EAN: | |
Weight: | 0.17 kg |
Length: | 0.00 m |
Width: | 0.00 m |