N0030A
Switching amplifiers for Namur sensors. NV1121/115VAC/RL/1D/1G
For the operation of intrinsically safe sensors in hazardous areas. Reliable short-circuit and wire-break monitoring. Easy programming of the output function. LED display to check operation, switching status and function. Quick and easy mounting on DIN rail
Application: | short-circuit monitoring; Wire monitoring |
Operating voltage tolerance [%]: | -10...10 |
Operating voltage [V]: | < 115 AC |
Max. power consumption [VA]: | 1 |
Number of channels: | 1 |
Electrical design: | relay; (1 changeover contact) |
Contact rating: | 253 V AC / 2 A / cos phi > 0,7 // 40 V DC / 2 A; (ohmic resistance) |
Switching frequency AC [Hz]: | 10 |
Ambient temperature [°C]: | -20...60 |
Protection: | IP 20 |
Approval: | PTB 02 ATEX 2035; IECEx PTB 17.0023 |
ATEX marking: | II (1) G [Ex ia Ga] IIC |
EMC: | EN 50081-2 (1993) EN 61326-1 (2006) |
EN 50081-2: | (1993) |
EN 61326-1: | (2006) |
MTTF [years]: | 458 |
Weight [g]: | 198 |
Switching cycles mechanical: | 10 million |
Display: | switching status LED, yellow operation LED, green function LED, red |
switching status: | LED, yellow |
operation: | LED, green |
function: | LED, red |
Remarks: | Caution The control monitor must be mounted outside the hazardous area. Free terminals must not be used. |
Pack quantity: | 1 pcs. |
Connection: | terminals: ...2.5 mm² |
in protection rating intrinsic safety: | [EEx ia] IIC |
Voltage [V]: | 10.6 |
Current [mA]: | 19.1 |
Power [mW]: | 51 |
External inductance [mH]: | 97 |
External capacitance [µF]: | 2.32 |
ECCN: | |
Country of Origin: | ID |
EAN: | |
Weight: | 0.20 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |