LR8300
Continuous level sensor (guided wave radar). LR0000B-BN34ASPKG/US
For the reliable level control in tanks and containers. Suitable for water and water-based media. Clearly visible 4-digit LED display. Modular system consisting of evaluation unit and probe. Adaptation to different container heights through shortening of the probe
Number of inputs and outputs: | Number of digital outputs: 4 |
Probe length L [mm]: | 100...1600 |
Process connection: | 3/4" NPT |
Special feature: | Gold-plated contacts |
Media: | Liquids |
Dielectric constant of the medium: | ≥ 5 |
Recommended media: | water; hydrous media |
Cannot be used for: | See the operating instructions, chapter "Function and features". |
Medium temperature [°C]: | -25...80; (90 < 1 h) |
Tank pressure [bar]: | -1...16 |
MAWP (for applications according to CRN) [bar]: | 16 |
Operating voltage [V]: | 18...30 DC |
Current consumption [mA]: | < 30 |
Protection class: | III |
Reverse polarity protection: | yes |
Power-on delay time [s]: | < 3 |
Number of inputs and outputs: | Number of digital outputs: 4 |
Total number of outputs: | 4 |
Output signal: | switching signal; IO-Link |
Electrical design: | PNP |
Number of digital outputs: | 4 |
Output function: | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V]: | 2.5 |
Permanent current rating of switching output DC [mA]: | 200 |
Short-circuit protection: | yes |
Type of short-circuit protection: | thermal, pulsed |
Overload protection: | yes |
Probe length L [mm]: | 100...1600 |
Active range A [mm]: | L-40 |
Inactive range I1 / I2 [mm]: | 30 / 10 |
Sampling rate [Hz]: | 4 |
Set point SP [mm]: | ≥ 15...L-30 |
Reset point rP [mm]: | ≥ 10...L-35 |
In steps of [mm]: | 5 |
Hysteresis [mm]: | > 5 |
Repeatability [mm]: | ± 5 |
Measuring error [mm]: | ± 7 |
Offset error [mm]: | 5 |
Resolution [mm]: | 1 |
Temperature drift per 10 K: | ± 0.2 % |
Communication interface: | IO-Link |
Transmission type: | COM2 (38,4 kBaud) |
IO-Link revision: | 1.1 |
SDCI standard: | IEC 61131-9 CDV |
IO-Link device ID: | 011 d / 00 00 B h |
Profiles: | no profile |
SIO mode: | yes |
Required master port type: | A |
Process data analogue: | 1 |
Process data binary: | 4 |
Min. process cycle time [ms]: | 2.3 |
Ambient temperature [°C]: | -25...60 |
Storage temperature [°C]: | -40...85 |
Protection: | IP 67 |
EMC: | DIN EN 61000-6-2 DIN EN 61000-6-3 in a closed metal tank DIN EN 61000-6-4 in plastic or open metal tanks |
DIN EN 61000-6-3: | in a closed metal tank |
DIN EN 61000-6-4: | in plastic or open metal tanks |
Shock resistance: | DIN EN 60068-2-27 50 g (11 ms) / 25 g (6 ms) with reference rod 0.5 m |
DIN EN 60068-2-27: | 50 g (11 ms) / 25 g (6 ms) with reference rod 0.5 m |
Vibration resistance: | DIN EN 60068-2-6 5 g (10...2000 Hz) / 1 g (5...200 Hz) with reference rod 0.5 m |
DIN EN 60068-2-6: | 5 g (10...2000 Hz) / 1 g (5...200 Hz) with reference rod 0.5 m |
MTTF [years]: | 205 |
Weight [g]: | 354.5 |
Materials: | stainless steel (1.4301 / 304); stainless steel (1.4404 / 316L) ; FKM; PBT; PC; PEI; TPE-V |
Materials (wetted parts): | stainless steel (1.4305 / 303); probe connection: stainless steel (1.4435 / 316L); PTFE; FKM |
Process connection: | 3/4" NPT |
Display: | Display unit 3 x LED, green switching status 4 x LED, yellow level alphanumeric display, 4-digit parameter setting alphanumeric display, 4-digit |
Display unit: | 3 x LED, green |
switching status: | 4 x LED, yellow |
level: | alphanumeric display, 4-digit |
parameter setting: | alphanumeric display, 4-digit |
Notes: | For 8-pole sockets the core colours are not standardised.; Please note the wiring of the sensor and the sockets (see data sheet).; Please see the technical note under "Downloads" |
Pack quantity: | 1 pcs. |
Connection: | Connector: 1 x M12; Contacts: gold-plated |
ECCN: | |
Country of Origin: | RO |
EAN: | |
Weight: | 0.35 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |