LR8010
Continuous level sensor (guided wave radar). LR0000B-BR34AVPKG/US
For the reliable level control in tanks and containers. Suitable for water, oils and coolants. When used as overflow precention to Federal Water Act WHG § 19. Modular system consisting of evaluation unit and probe. Adaptation to different container heights through shortening of the probe
Number of inputs and outputs: | Number of digital outputs: 4 |
Probe length L [mm]: | 100...1600 |
Process connection: | G 3/4 external thread |
Special feature: | Gold-plated contacts |
Installation: | Operation only in conjunction with rod and coaxial pipe. |
Media: | hydrous coolants; oils; oil-based media; water; media similar to water |
Dielectric constant of the medium: | ≥ 2 |
Cannot be used for: | See the operating instructions, chapter "Function and features". |
Medium temperature [°C]: | 0...80 |
Tank pressure [bar]: | -0.5...4 |
Operating voltage [V]: | 18...30 DC |
Current consumption [mA]: | < 65 |
Protection class: | III |
Reverse polarity protection: | yes |
Power-on delay time [s]: | < 3 |
Number of inputs and outputs: | Number of digital outputs: 4 |
Total number of outputs: | 4 |
Output signal: | switching signal |
Electrical design: | PNP |
Number of digital outputs: | 4 |
Output function: | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V]: | 2.5 |
Permanent current rating of switching output DC [mA]: | 200 |
Short-circuit protection: | yes |
Type of short-circuit protection: | thermal, pulsed |
Overload protection: | yes |
Probe length L [mm]: | 100...1600 |
Active range A [mm]: | L-40 (L-60); (when set to oil and oil based media) |
Inactive range I1 / I2 [mm]: | 30 / 10 (30); (when set to oil and oil based media) |
Set point SP [mm]: | ≥ 15 (35) / ≤ L-30 |
Note on setpoint SP: | when set to oil and oil based media |
Reset point rP [mm]: | ≥ 10 (30) / ≤ L-35 |
Note on reset point rP: | when set to oil and oil based media |
In steps of [mm]: | 5 |
Hysteresis [mm]: | > 5 |
Overflow switch point OP [mm]: | 70...L-30 |
Hysteresis, OP [mm]: | 10 |
Repeatability [mm]: | ± 5 |
Switch point accuracy [mm]: | ± (15 + 0,5 % ); (% of the final value of the measuring range: L - 30 mm) |
Ambient temperature [°C]: | 0...60 |
Storage temperature [°C]: | -25...80 |
Protection: | IP 67 |
Approval: | WHG § 19 |
EMC: | DIN EN 61000-6-2 DIN EN 61000-6-4 |
Shock resistance: | DIN EN 60068-2-27 50 g (11 ms) |
DIN EN 60068-2-27: | 50 g (11 ms) |
Vibration resistance: | DIN EN 60068-2-6 5 g (10...2000 Hz) |
DIN EN 60068-2-6: | 5 g (10...2000 Hz) |
MTTF [years]: | 183 |
Weight [g]: | 402 |
Materials: | stainless steel (1.4404 / 316L); stainless steel (1.4301 / 304); FKM; PBT-GF20; PC; PEI; TPV |
Materials (wetted parts): | stainless steel (1.4305 / 303); probe connection: stainless steel (1.4435 / 316L); PTFE; FKM; Sealing: NBR-PPTA 20 |
Process connection: | G 3/4 external thread |
Display: | Display unit 3 x LED, green switching status 4 x LED, yellow level alphanumeric display, 4-digit parameter setting alphanumeric display, 4-digit |
Display unit: | 3 x LED, green |
switching status: | 4 x LED, yellow |
level: | alphanumeric display, 4-digit |
parameter setting: | alphanumeric display, 4-digit |
Notes: | For 8-pole sockets the core colours are not standardised.; Please note the wiring of the sensor and the sockets (see data sheet). |
Pack quantity: | 1 pcs. |
Connection: | Connector: 1 x M12; Contacts: gold-plated |
ECCN: | |
Country of Origin: | DE |
EAN: | |
Weight: | 0.40 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |