Ifm LMC410

Sensor for point level detection. LMGCE-C12E-QSKG-1/US

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

For the reliable level control in tanks and containers. Two programmable switching outputs, one of them with IO-Link communication interface. Preset to oil and oil-based media. Simple process connection via screw-in adapter. Reliable suppression of deposits or foam

Technical parameters

Number of inputs and outputs: Number of digital outputs: 2
Factory setting: oils; oil-based media
Process connection: G 1/2 external thread
Special feature: Gold-plated contacts
Media: water; hydrous media; oils; oil-based media; coolants; powder
Cannot be used for: See the operating instructions, chapter "Function and features".
Medium temperature [°C]: -25...100
Probe length [mm]: 9.6
Tank pressure [bar]: -1...40
MAWP (for applications according to CRN) [bar]: 40
Medium temperature [°C]: -25...100
Operating voltage [V]: 18...30 DC
Current consumption [mA]: < 35
Protection class: III
Reverse polarity protection: yes
Number of inputs and outputs: Number of digital outputs: 2
Total number of outputs: 2
Output signal: switching signal; IO-Link
Electrical design: PNP/NPN
Number of digital outputs: 2
Output function: normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V]: 2.5
Permanent current rating of switching output DC [mA]: 50; (100 (...60 °C))
Short-circuit protection: yes
Type of short-circuit protection: thermal, pulsed
Overload protection: yes
Factory setting: oils; oil-based media
Response time [s]: < 0.5
Communication interface: IO-Link
Transmission type: COM2 (38,4 kBaud)
IO-Link revision: 1.1
SDCI standard: IEC 61131-9
IO-Link device ID: 0x0002A3
Profiles: Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis
SIO mode: yes
Required master port type: A
Process data analogue: 1
Process data binary: 2
Min. process cycle time [ms]: 2.3
Ambient temperature [°C]: -25...85
Note on ambient temperature: for installation in probe observe the temperature in the pipe, see installation instructions
Storage temperature [°C]: -40...85
Protection: IP 68; IP 69K; (7 days / 1 m water depth / 0.1 bar: IP 68)
EMC: DIN EN 61000-6-2 DIN EN 61000-6-3 : closed tanks DIN EN 61000-6-4 : open tanks
DIN EN 61000-6-3: : closed tanks
DIN EN 61000-6-4: : open tanks
Shock resistance: DIN EN 60068-2-27 50 g (11 ms)
DIN EN 60068-2-27: 50 g (11 ms)
Vibration resistance: DIN EN 60068-2-6 20 g (10...2000 Hz)
DIN EN 60068-2-6: 20 g (10...2000 Hz)
MTTF [years]: 534
UL approval: UL Approval no. H004
UL Approval no.: H004
Weight [g]: 127.5
Dimensions [mm]: Ø 18.1 / L = 76.2
Materials: stainless steel (1.4404 / 316L); PEEK; PEI; FKM
Materials (wetted parts): stainless steel (1.4404 / 316L); PEEK; FKM
Process connection: G 1/2 external thread
Display: switching status LEDs, yellow operating status LEDs, green
switching status: LEDs, yellow
operating status: LEDs, green
Pack quantity: 1 pcs.
Connection: Connector: 1 x M12; Contacts: gold-plated

Logistic parameters

ECCN:
Country of Origin: DE
EAN:
Weight: 0.13 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m