LMC400
Sensor for point level detection. LMGCE-C12E-QSKG-0/US
For the reliable level control in tanks and containers. Two programmable switching outputs, one of them with IO-Link communication interface. Preset to water and hydrous media. Simple process connection via screw-in adapter. Reliable suppression of deposits or foam
Number of inputs and outputs: | Number of digital outputs: 2 |
Factory setting: | water; hydrous media |
Process connection: | G 1/2 external thread |
Special feature: | Gold-plated contacts |
Media: | water; hydrous media; oils; oil-based media; coolants; powder |
Cannot be used for: | See the operating instructions, chapter "Function and features". |
Medium temperature [°C]: | -25...100 |
Probe length [mm]: | 9.6 |
Tank pressure [bar]: | -1...40 |
MAWP (for applications according to CRN) [bar]: | 40 |
Medium temperature [°C]: | -25...100 |
Operating voltage [V]: | 18...30 DC |
Current consumption [mA]: | < 35 |
Protection class: | III |
Reverse polarity protection: | yes |
Number of inputs and outputs: | Number of digital outputs: 2 |
Total number of outputs: | 2 |
Output signal: | switching signal; IO-Link |
Electrical design: | PNP/NPN |
Number of digital outputs: | 2 |
Output function: | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V]: | 2.5 |
Permanent current rating of switching output DC [mA]: | 50; (100 (...60 °C)) |
Short-circuit protection: | yes |
Type of short-circuit protection: | thermal, pulsed |
Overload protection: | yes |
Factory setting: | water; hydrous media |
Response time [s]: | < 0.5 |
Communication interface: | IO-Link |
Transmission type: | COM2 (38,4 kBaud) |
IO-Link revision: | 1.1 |
SDCI standard: | IEC 61131-9 |
IO-Link device ID: | 0x0002A2 |
Profiles: | Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis |
SIO mode: | yes |
Required master port type: | A |
Process data analogue: | 1 |
Process data binary: | 2 |
Min. process cycle time [ms]: | 2.3 |
Ambient temperature [°C]: | -25...85 |
Note on ambient temperature: | for installation in probe observe the temperature in the pipe, see installation instructions |
Storage temperature [°C]: | -40...85 |
Protection: | IP 68; IP 69K; (7 days / 1 m water depth / 0.1 bar: IP 68) |
EMC: | DIN EN 61000-6-2 DIN EN 61000-6-3 : closed tanks DIN EN 61000-6-4 : open tanks |
DIN EN 61000-6-3: | : closed tanks |
DIN EN 61000-6-4: | : open tanks |
Shock resistance: | DIN EN 60068-2-27 50 g (11 ms) |
DIN EN 60068-2-27: | 50 g (11 ms) |
Vibration resistance: | DIN EN 60068-2-6 20 g (10...2000 Hz) |
DIN EN 60068-2-6: | 20 g (10...2000 Hz) |
MTTF [years]: | 534 |
UL approval: | UL Approval no. H004 |
UL Approval no.: | H004 |
Weight [g]: | 127.5 |
Dimensions [mm]: | Ø 18.1 / L = 76.2 |
Materials: | stainless steel (1.4404 / 316L); PEEK; PEI; FKM |
Materials (wetted parts): | stainless steel (1.4404 / 316L); PEEK; FKM |
Process connection: | G 1/2 external thread |
Display: | switching status LEDs, yellow operating status LEDs, green |
switching status: | LEDs, yellow |
operating status: | LEDs, green |
Pack quantity: | 1 pcs. |
Connection: | Connector: 1 x M12; Contacts: gold-plated |
ECCN: | |
Country of Origin: | DE |
EAN: | |
Weight: | 0.13 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |