KX5002
Capacitive NAMUR sensor. KX-2015-N/NI/6M/1D/1G
For applications in hazardous areas. Easy setting of the sensing range via potentiometer. Clearly visible indication of the switching status by LED. For connection to intrinsically safe circuits. High mechanical stability thanks to robust metal housing
Electrical design: | NAMUR |
Output function: | normally closed |
Sensing range [mm]: | 15 |
Housing: | threaded type |
Dimensions [mm]: | M34 x 1.5 / L = 92 |
Connection to switching amplifiers: | yes |
Switching amplifiers: | connection to certified intrinsically safe circuits with the max. values: U = 15 V / I = 50 mA / P = 120 mW |
Nominal voltage DC [V]: | 8.2; (1kΩ) |
Supply voltage DC [V]: | 7.5...15 |
Current consumption [mA]: | < 1; (disabled; conductive: > 2,2) |
Protection class: | I |
Electrical design: | NAMUR |
Output function: | normally closed |
Switching frequency DC [Hz]: | 40 |
Sensing range [mm]: | 15 |
Sensing range adjustable: | yes |
Factory setting sensing range [mm]: | 15 |
Correction factor: | glass: 0.4 / water: 1 / ceramics: 0.2 / PVC: 0.2 |
Hysteresis [% of Sr]: | 1...15 |
Switch point drift [% of Sr]: | -15...15 |
Ambient temperature [°C]: | -20...60 |
Protection: | IP 65 |
Approval: | DMT 01 ATEX E 020 |
ATEX marking: | II 1G Ex ia IIB T6 Ga |
EMC: | EN 60947-5-2 |
MTTF [years]: | 838 |
Max. internal capacitance [nF]: | 375.64 |
Max. internal inductance [µH]: | 3 |
Weight [K40]: | 650.5 |
Housing: | threaded type |
Mounting: | non-flush mountable |
Dimensions [mm]: | M34 x 1.5 / L = 92 |
Thread designation: | M34 x 1.5 |
Materials: | brass white bronze coated; sensing face: PTFE |
Display: | switching status 1 x LED, yellow |
switching status: | 1 x LED, yellow |
Pack quantity: | 1 pcs. |
Connection: | Cable: 6 m, PVC; 3 x 0.5 mm² |
ECCN: | |
Country of Origin: | DE |
EAN: | |
Weight: | 0.65 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |