IX5006
Position sensor for rising stem valves. IX-3080-BPKG/3LED
Position feedback for single and double seat valve and for diaphragm valves. Freely selectable switching outputs: valve open / closed, seat lift. Replaces three binary pulse pick-ups. Resolution of 0.2 mm across the entire measuring range. Programming of valve positions with pushbuttons
Electrical design: | PNP |
Output function: | 3 x normally open |
Dimensions [mm]: | 67.5 x 43 x 110 |
Application: | position feedback for seat valves and diaphragm valves; absolute distance measurement; monitoring of the valve seal |
Operating voltage [V]: | 18...36 DC |
Current consumption [mA]: | 42; (24 V) |
Protection class: | III |
Reverse polarity protection: | yes |
Max. power-on delay time [ms]: | 2000 |
Electrical design: | PNP |
Output function: | 3 x normally open |
Max. voltage drop switching output DC [V]: | 2.5 |
Permanent current rating of switching output DC [mA]: | 100 |
Short-circuit protection: | yes |
Type of short-circuit protection: | pulsed |
Overload protection: | yes |
Measuring range [mm]: | 0...80 |
Max. target speed [m/s]: | 1 |
Resolution of valve stroke [mm]: | 0.2 |
Target: | cylindrical disc - Ø 24 mm ±0,05 mm - minimum height 10 mm - flat surface - stainless steel to DIN17440, material number 316S12. |
-: | Ø 24 mm ±0,05 mm |
-: | minimum height 10 mm |
-: | flat surface |
-: | stainless steel to DIN17440, material number 316S12. |
Parameter setting options: | 3 switch points to be freely defined within the measuring range |
Ambient temperature [°C]: | -25...85 |
Note on ambient temperature: | for firmly laid cable |
Protection: | IP 65; IP 67; (only in conjunction with an installation in the valve head that provides sufficient protection against mechanical damage of the sensor) |
EMC: | EN 61000-4-2 ESD 4 kV CD / 8 kV AD EN 61000-4-3 HF radiated 10 V/m EN 61000-4-4 Burst 2 kV coupling clamp EN 61000-4-6 HF conducted 3 V |
EN 61000-4-2 ESD: | 4 kV CD / 8 kV AD |
EN 61000-4-3 HF radiated: | 10 V/m |
EN 61000-4-4 Burst: | 2 kV coupling clamp |
EN 61000-4-6 HF conducted: | 3 V |
MTTF [years]: | 298 |
Weight [g]: | 217 |
Dimensions [mm]: | 67.5 x 43 x 110 |
Materials: | PA; TPE; PP; LCP |
Display: | switching status 1 x LED, green open switching status 1 x LED, yellow seat switching status 1 x LED, red close |
switching status: | 1 x LED, green open |
switching status: | 1 x LED, yellow seat |
switching status: | 1 x LED, red close |
Accessories (supplied): | mounting clamps: 1 |
Pack quantity: | 1 pcs. |
Connection: | Cable: 2 m, PVC; 5 x 0.14 mm² |
ECCN: | |
Country of Origin: | DE |
EAN: | |
Weight: | 0.22 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |