IM5175
Inductive analogue sensor with IO-Link. IMC4035A2PKG/F/IO/US
Electrical design: | PNP/NPN; (parameterisable) |
Output function: | normally open / normally closed; (parameterisable) |
Communication interface: | IO-Link |
Housing: | rectangular |
Dimensions [mm]: | 40 x 40 x 54 |
Operating voltage [V]: | 15...30 DC |
Current consumption [mA]: | < 33 |
Protection class: | II |
Reverse polarity protection: | yes |
Electrical design: | PNP/NPN; (parameterisable) |
Output function: | normally open / normally closed; (parameterisable) |
Max. voltage drop switching output DC [V]: | 2.5 |
Permanent current rating of switching output DC [mA]: | 100 |
Switching frequency DC [Hz]: | 100 |
Analogue voltage output [V]: | 0...10; (linear; gradient: 0,3125 V/mm; for frontal approach and for target made of mild steel: 105 x 105 x 1 mm) |
Min. load resistance [Ω]: | 2000 |
Short-circuit protection: | yes |
Overload protection: | yes |
Measuring range [mm]: | 3...35 |
Switch point IO-Link [mm]: | 6.13...32.69 |
Correction factor: | steel: 1 / stainless steel: 0.8 / brass: 0.5 / aluminium: 0.5 / copper: 0.4 |
Hysteresis [% of Sr]: | 3...15 |
Note on hysteresis: | parameterisable |
Linearity error of analogue output [%]: | ± 2; (of the final value of the measuring range) |
Repeatability analogue output [%]: | ± 2; (of the final value of the measuring range) |
Temperature coefficient [%/K vom MEW]: | ±0,15 |
Temperature drift [% vom MEW]: | ±5 |
Response time [ms]: | < 20 |
Communication interface: | IO-Link |
Transmission type: | COM2 (38,4 kBaud) |
IO-Link revision: | 1.1 |
SDCI standard: | IEC 61131-9 |
IO-Link device ID: | 1206d / 0004B6h |
Profiles: | Smart Sensor: Identification and diagnosis; Multi-channel, two setpoint switching sensor, type 0 Generic Profiled Sensor; Teach Channel |
SIO mode: | yes |
Required master port type: | A |
Min. process cycle time [ms]: | 3.2 |
IO-Link process data (cyclical): | function bit length process value 16 device status 4 binary switching information 2 |
function: | bit length |
process value: | 16 |
device status: | 4 |
binary switching information: | 2 |
IO-Link functions (acyclical): | switching cycles counter; switch-on cycle counter; operating hours counter; internal temperature; application specific tag |
Note: | For further information please see the IODD PDF file under "Downloads" |
Ambient temperature [°C]: | -25...80 |
Protection: | IP 67 |
EMC: | EN 61000-4-2 ESD 4 kV CD / 8 kV AD EN 61000-4-3 HF radiated 10 V/m EN 61000-4-4 Burst 2 kV EN 61000-4-6 HF conducted 10 V EN 55011 class B |
EN 61000-4-2 ESD: | 4 kV CD / 8 kV AD |
EN 61000-4-3 HF radiated: | 10 V/m |
EN 61000-4-4 Burst: | 2 kV |
EN 61000-4-6 HF conducted: | 10 V |
EN 55011: | class B |
MTTF [years]: | 231 |
UL approval: | Ta -25...70 °C Enclosure type Type 1 voltage supply Limited Voltage/Current UL Approval no. A026 File number UL E174191 |
Ta: | -25...70 °C |
Enclosure type: | Type 1 |
voltage supply: | Limited Voltage/Current |
UL Approval no.: | A026 |
File number UL: | E174191 |
Weight [g]: | 158.5 |
Housing: | rectangular |
Mounting: | non-flush mountable |
Dimensions [mm]: | 40 x 40 x 54 |
Materials: | PA; stainless steel (1.4404 / 316L) |
Display: | target in measuring range 1 x LED, yellow lights target outside measuring range 1 x LED, yellow flashing operation LED, green |
target in measuring range: | 1 x LED, yellow lights |
target outside measuring range: | 1 x LED, yellow flashing |
operation: | LED, green |
Remarks: | Installation only with stainless steel plate 16x40x3 and 2 cylinder screws ISO 4762-12.9 |
Pack quantity: | 1 pcs. |
Connection: | Connector: 1 x M12 |
ECCN: | |
Country of Origin: | DE |
EAN: | |
Weight: | 0.16 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |