IM5173
Inductive sensor with IO-Link. IMC3026-FRKG/IO/US-100
Long sensing range for use in conveying. Reliable transmission of the distance as linearised process value via IO-Link. Five positions of the sensing face selectable. LED display to check switching status and operation. Normally closed / normally open and PNP/NPN adjustable via IO-Link
Electrical design: | PNP/NPN; (parameterisable) |
Output function: | normally open / normally closed; (selectable) |
Communication interface: | IO-Link |
Housing: | rectangular |
Dimensions [mm]: | 40 x 40 x 54 |
Operating voltage [V]: | 10...30 DC |
Current consumption [mA]: | 10 |
Protection class: | III |
Reverse polarity protection: | yes |
Electrical design: | PNP/NPN; (parameterisable) |
Output function: | normally open / normally closed; (selectable) |
Max. voltage drop switching output DC [V]: | 2.5 |
Permanent current rating of switching output DC [mA]: | 100 |
Switching frequency DC [Hz]: | 100 |
Short-circuit protection: | yes |
Overload protection: | yes |
Switch point IO-Link [mm]: | 4.9...24.5; (parameterisable) |
Measuring range IO-Link [mm]: | 2.6...26 |
Correction factor: | steel: 1 / stainless steel: 0.8 / brass: 0.4 / aluminium: 0.4 / copper: 0.3 |
Hysteresis [% of Sr]: | 3...15 |
Linearity error of analogue output [%]: | ± 2 %; (of the final value of the measuring range) |
Repeatability analogue output [%]: | ± 1 %; (of the final value of the measuring range) |
Temperature coefficient: | ± 0,2 %/K; (of the final value of the measuring range) |
Communication interface: | IO-Link |
Transmission type: | COM2 (38,4 kBaud) |
IO-Link revision: | 1.1 |
SDCI standard: | IEC 61131-9 CDV |
IO-Link device ID: | 791d / 000317h |
Profiles: | Smart Sensor: Device Identification; Device Diagnosis; Device Teach Channel; Binary Data Channel; Process Data Variable |
SIO mode: | yes |
Required master port type: | A |
Min. process cycle time [ms]: | 3 |
Ambient temperature [°C]: | -25...80 |
Protection: | IP 67 |
EMC: | EN 61000-4-2 ESD 4 kV CD / 8 kV AD EN 61000-4-3 HF radiated 10 V/m EN 61000-4-4 Burst 2 kV EN 61000-4-6 HF conducted 10 V EN 55011 class B |
EN 61000-4-2 ESD: | 4 kV CD / 8 kV AD |
EN 61000-4-3 HF radiated: | 10 V/m |
EN 61000-4-4 Burst: | 2 kV |
EN 61000-4-6 HF conducted: | 10 V |
EN 55011: | class B |
MTTF [years]: | 629 |
UL approval: | Ta -25...70 °C Enclosure type Type 1 voltage supply Limited Voltage/Current UL Approval no. A009 File number UL E174191 |
Ta: | -25...70 °C |
Enclosure type: | Type 1 |
voltage supply: | Limited Voltage/Current |
UL Approval no.: | A009 |
File number UL: | E174191 |
Weight [g]: | 151.5 |
Housing: | rectangular |
Sensing face: | 5 positions selectable |
Mounting: | non-flush mountable |
Dimensions [mm]: | 40 x 40 x 54 |
Materials: | PA; connector thread: brass white bronze coated |
Display: | operation LED, green SIO mode output stage supplied with current LED, yellow lights IO-Link mode target in measuring range LED, yellow lights |
operation: | LED, green |
output stage supplied with current: | LED, yellow lights |
target in measuring range: | LED, yellow lights |
Pack quantity: | 1 pcs. |
Connection: | Connector: 1 x M12 |
ECCN: | |
Country of Origin: | RO |
EAN: | |
Weight: | 0.15 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |