Ifm IIT001

Inductive sensor. IIK2014BARKA/M/V4A/LS-104-AK

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

Wide operating temperature range. Temperature shock resistant even in case of frequent temperature fluctuations. Robust stainless steel housing for use in the food and beverage industry. Resistant to high-pressure cleaning with aggressive cleaning agents. High protection rating for the requirements of harsh industrial environments

Technical parameters

Output function: normally open
Sensing range [mm]: 14
Housing: threaded type
Dimensions [mm]: M30 x 1.5 / L = 70
Special feature: Gold-plated contacts
Application: regular cleaning processes
Operating voltage [V]: 20...140 AC/DC
Protection class: II
Reverse polarity protection: yes
Max. power-on delay time [ms]: 1000
Output function: normally open
Max. voltage drop switching output DC [V]: 5.5
Max. voltage drop switching output AC [V]: 5.5
Minimum load current [mA]: 5
Max. leakage current [mA]: 1
Permanent current rating of switching output AC [mA]: 80; (200 (...80 °C))
Permanent current rating of switching output DC [mA]: 80; (200 (...80 °C))
Short-time current rating of switching output [mA]: 1200; (20ms / 0,5Hz / 80 mA (> 80°C))
Switching frequency AC [Hz]: 25
Switching frequency DC [Hz]: 100
Short-circuit protection: yes
Type of short-circuit protection: pulsed
Overload protection: yes
Sensing range [mm]: 14
Operating distance [mm]: 0...11.34
Correction factor: steel: 1 / stainless steel: 0.7 / brass: 0.5 / aluminium: 0.4 / copper: 0.3
Hysteresis [% of Sr]: 2...15
Ambient temperature [°C]: 0...100
Protection: IP 68; IP 69K; ("COP")
EMC: EN 61000-4-2 ESD 4 kV CD / 8 kV AD EN 61000-4-3 HF radiated 10 V/m EN 61000-4-4 Burst 2 kV EN 61000-4-6 HF conducted 10 V EN 55011 class B
EN 61000-4-2 ESD: 4 kV CD / 8 kV AD
EN 61000-4-3 HF radiated: 10 V/m
EN 61000-4-4 Burst: 2 kV
EN 61000-4-6 HF conducted: 10 V
EN 55011: class B
MTTF [years]: 380
UL approval: Ta 0...40 °C Enclosure type Type 1 voltage supply Hazardous voltage File number UL E174191
Ta: 0...40 °C
Enclosure type: Type 1
voltage supply: Hazardous voltage
File number UL: E174191
Weight [g]: 140.8
Housing: threaded type
Mounting: flush mountable
Dimensions [mm]: M30 x 1.5 / L = 70
Thread designation: M30 x 1.5
Materials: housing: stainless steel (1.4404 / 316L); sensing face: PEEK; lock nuts: stainless steel (1.4404 / 316L)
Display: switching status 4 x 90° LED, yellow
switching status: 4 x 90° LED, yellow
Accessories (supplied): lock nuts: 2
Pack quantity: 1 pcs.

Logistic parameters

ECCN:
Country of Origin: RO
EAN:
Weight: 0.14 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m