IA0032
Inductive sensor. IAE2010-FBOA..
With combined AC/DC output stage. Two-wire technology. Smooth plastic housing to protect against deposits. With terminal chamber that can be rotated by 90°. High protection rating for the requirements of harsh industrial environments
Output function: | normally open / normally closed; (selectable) |
Sensing range [mm]: | 10 |
Housing: | cylindrical |
Dimensions [mm]: | Ø 20 / L = 92 |
Operating voltage [V]: | 20...250 AC/DC |
Protection class: | II |
Reverse polarity protection: | no |
Output function: | normally open / normally closed; (selectable) |
Max. voltage drop switching output DC [V]: | 6 |
Max. voltage drop switching output AC [V]: | 6.5 |
Minimum load current [mA]: | 5 |
Max. leakage current [mA]: | 2.5 (250 V AC) / 1.3 (110 V AC) / 0.8 (24 V DC) |
Permanent current rating of switching output AC [mA]: | 250; (350 (...50 °C)) |
Permanent current rating of switching output DC [mA]: | 100 |
Short-time current rating of switching output [mA]: | 2200; (20 ms / 0,5 Hz) |
Switching frequency AC [Hz]: | 25 |
Switching frequency DC [Hz]: | 70 |
Short-circuit proof: | no |
Overload protection: | no |
Sensing range [mm]: | 10 |
Real sensing range Sr [mm]: | 10 ± 10 % |
Operating distance [mm]: | 0...8.1 |
Correction factor: | steel: 1 / stainless steel: 0.7 / brass: 0.4 / aluminium: 0.3 / copper: 0.2 |
Hysteresis [% of Sr]: | 1...15 |
Switch point drift [% of Sr]: | -10...10 |
Ambient temperature [°C]: | -25...80 |
Protection: | IP 65 |
EMC: | EN 60947-5-2 EN 55011 class B |
EN 55011: | class B |
MTTF [years]: | 606 |
UL approval: | Ta 0...40 °C Enclosure type Type 1 voltage supply Hazardous voltage File number UL E174191 |
Ta: | 0...40 °C |
Enclosure type: | Type 1 |
voltage supply: | Hazardous voltage |
File number UL: | E174191 |
Weight [g]: | 85 |
Housing: | cylindrical |
Mounting: | non-flush mountable |
Dimensions [mm]: | Ø 20 / L = 92 |
Materials: | PBT; LED window: PC |
Display: | switching status 1 x LED, yellow |
switching status: | 1 x LED, yellow |
Required protection: | miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting |
Accessories (supplied): | Mounting clamps: 1 |
Remarks: | Recommendation: Check the safe functioning of the unit after a short circuit. |
Pack quantity: | 1 pcs. |
Connection: | terminals: ...2.5 mm²; Cable sheath: Ø 4.5...10 mm; Cable gland: M16 X 1.5 |
ECCN: | |
Country of Origin: | RO |
EAN: | |
Weight: | 0.09 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |