DN4033
Switched-mode power supply 24 V DC. PSU-3AC/24VDC-10A
For the regulated power supply for controllers, sensors, actuators, and industrial electronics. Low power loss thanks to high efficiency. High mains buffering time. Particularly space-saving design. High power reserves
Frequency AC [Hz]: | 47...64 |
Operating voltage tolerance [%]: | 15...20 |
Nominal voltage AC [V]: | < 400 |
Input voltage range AC [V]: | 380...480 |
Output voltage DC [V]: | 24...28 |
Protection class: | I; (IEC 61140) |
Overvoltage protection: | yes; (< 32 DC) |
Output voltage [V]: | adjustable; output voltage to SELV, PELV |
Max. output current at min. output voltage [A]: | 10 |
Max. output current at max. output voltage [A]: | 8.6 |
Max. output current peak at min. output voltage [A]: | 12 |
Max. output current peak at max. output voltage [A]: | 10.3 |
Output power (permanent) [W]: | 240 |
Output power (peak) [W]: | 288 |
Note on output power (peak): | ≤ 45 °C permitted continuously; > 45 °C < 1 minute every 10 minutes |
Power factor (nominal voltage 400 V AC / 50 Hz): | 0.53 |
Note on power factor (nominal voltage 400 V AC / 50 Hz): | with symmetrical phase voltage |
Power factor (nominal voltage 480 V AC / 50 Hz): | 0.52 |
Note on power factor (nominal voltage 480 V AC / 50 Hz): | with symmetrical phase voltage |
Power reserve [%]: | 20 |
Number of output circuits: | 1 |
Max. residual ripple [mV]: | 50 |
Switch-on peak current (nominal voltage 400 V AC / 60 Hz) [A]: | 4 |
Switch-on peak current (nominal voltage 480 V AC / 50 Hz) [A]: | 4 |
Inrush current limitation: | yes |
Efficiency (nominal voltage 400 V AC / 60 Hz) [%]: | 92.8 |
Efficiency (nominal voltage 480 V AC / 50 Hz) [%]: | 92.9 |
External input protection: | ≤ B-6 A / ≤ C-3 A |
Derating [W/K]: | 6 (60...70 °C) |
Mains buffering time (nominal voltage 400 V AC / 60 Hz) [ms]: | 34 |
Mains buffering time (nominal voltage 480 V AC / 50 Hz) [ms]: | 54 |
Input current (nominal voltage 400 V AC / 60 Hz) [A]: | 0.7 |
Input current (nominal voltage 480 V AC / 50 Hz) [A]: | 0.6 |
Power loss (nominal voltage 400 V AC / 60 Hz) [W]: | 18.6 |
Power loss (nominal voltage 480 V AC / 50 Hz) [W]: | 18.3 |
Back feeding protection [V]: | 35 |
Short-circuit proof: | yes |
Overload protection: | yes |
Overload performance: | output current constant |
Type DC-OK signal: | relay output |
Reliability of the DC OK signal: | 60 V DC (0.3 A) / 30 V DC (1 A) / 30 V AC (0.5 A) |
Ambient temperature [°C]: | -25...70 |
Note on ambient temperature: | observe the free space for convection (see operating instructions) |
Storage temperature [°C]: | -40...85 |
Max. relative air humidity [%]: | 95; (IEC 60068-2-30) |
Protection: | IP 20; (EN 60529) |
Degree of soiling: | 2; (IEC 62103: conductive soiling not permitted) |
EMC: | EN 61000-6-1 EN 61000-6-2 EN 61000-6-3 EN 61000-6-4 EN 61000-3-2 Class A |
EN 61000-3-2: | Class A |
Vibration resistance: | IEC 60068-2-6 ±1,6 mm 2...17,8 Hz / 2 g 17,8...500 Hz |
IEC 60068-2-6: | ±1,6 mm 2...17,8 Hz / 2 g 17,8...500 Hz |
Shock resistance: | IEC 60068-2-27 30 g 6 ms / 20 g 11 ms |
IEC 60068-2-27: | 30 g 6 ms / 20 g 11 ms |
Power Factor Correction (PFC): | met |
Weight [K40]: | 883 |
Type of mounting: | rail; (TH35 (EN 60715)) |
Dimensions [mm]: | 124 x 62 x 122.5 |
Materials: | steel sheet |
Display: | DC ok 1 x LED |
DC ok: | 1 x LED |
Remarks: | Series connection of outputs only applies to identical units up to max. 150 V DC overall voltage |
Pack quantity: | 1 pcs. |
Connection: | screw terminals: |
ECCN: | |
Country of Origin: | CN |
EAN: | |
Weight: | 0.88 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |