DN1042
Switched-mode power supply 24 V DC. PSU-1AC/200-240VAC/24VDC-5A
| Frequency AC [Hz]: | 47...63 |
| Operating voltage tolerance [%]: | 10 |
| Nominal voltage AC [V]: | 230 |
| Input voltage range AC [V]: | 200...240 |
| Output voltage DC [V]: | 24...28 |
| Protection class: | I; (IEC 61140) |
| Overvoltage protection: | yes; (< 34 V DC) |
| Output voltage [V]: | adjustable; output voltage to SELV, PELV |
| Max. output current at min. output voltage [A]: | 5 |
| Max. output current at max. output voltage [A]: | 4.3 |
| Max. output current peak at min. output voltage [A]: | 6 |
| Max. output current peak at max. output voltage [A]: | 5.1 |
| Output power (permanent) [W]: | 120 |
| Power factor (nominal voltage 230 V AC / 50 Hz): | 0.54 |
| Number of output circuits: | 1 |
| Max. residual ripple [mV]: | 100 |
| Switch-on peak current (nominal voltage 230 V AC / 50 Hz) [A]: | 28 |
| Efficiency (nominal voltage 230 V AC / 50 Hz) [%]: | 90.5 |
| External input protection: | ≤ B-10 A / ≤ C-6 A |
| Derating [W/K]: | 3 (55...70 °C) |
| Mains buffering time (nominal voltage 230 V AC / 50 Hz) [ms]: | 60 |
| Input current (nominal voltage 230 V AC / 50 Hz) [A]: | 1.06 |
| Power loss (nominal voltage 230 V AC / 50 Hz) [W]: | 12.6 |
| Back feeding protection [V]: | 35 |
| Short-circuit proof: | yes |
| Overload protection: | yes |
| Overload performance: | output current constant |
| Parallel connection of outputs possible: | no |
| Series connection of outputs possible: | yes |
| Ambient temperature [°C]: | -10...70 |
| Note on ambient temperature: | observe the free space for convection (see operating instructions) |
| Storage temperature [°C]: | -40...85 |
| Max. relative air humidity [%]: | 95; (IEC 60068-2-30) |
| Protection: | IP 20; (EN 60529) |
| Degree of soiling: | 2; (IEC 62103: conductive soiling not permitted) |
| EMC: | EN 61000-6-1 EN 61000-6-2 EN 61000-6-4 |
| Vibration resistance: | IEC 60068-2-6 ±1,6 mm 2...17,8 Hz / 2 g 17,8...500 Hz |
| IEC 60068-2-6: | ±1,6 mm 2...17,8 Hz / 2 g 17,8...500 Hz |
| Shock resistance: | IEC 60068-2-27 30 g 6 ms / 20 g 11 ms |
| IEC 60068-2-27: | 30 g 6 ms / 20 g 11 ms |
| Weight [g]: | 372.5 |
| Type of mounting: | rail; (TH35 (EN 60715)) |
| Dimensions [mm]: | 124 x 39 x 129 |
| Materials: | PC |
| Display: | DC ok 1 x LED |
| DC ok: | 1 x LED |
| Remarks: | Series connection of outputs only applies to identical units up to max. 150 V DC overall voltage UL 508 (Industrial Control Equipment) |
| Pack quantity: | 1 pcs. |
| Connection: | screw terminals: |
| ECCN: | |
| Country of Origin: | CN |
| EAN: | |
| Weight: | 0.37 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |