DI103A
Compact evaluation unit for speed monitoring. DIA2010-ZROA/5-3600 I/MIN/3D
For applications in hazardous areas. Reliable non-contact monitoring of the rotational speed with regard to underspeed. 2 in 1: speed sensor and evaluation in one compact housing. Easy setting of the switch point via potentiometer. For direct connection to a PLC
| Output function: | normally open |
| Sensing range [mm]: | 10 |
| Dimensions [mm]: | M30 x 1.5 / L = 80 |
| Application: | simple evaluation of rotating and linear movement with regard to underspeed; blocking |
| Nominal voltage AC [V]: | 20...250 |
| Nominal voltage DC [V]: | 20...250 |
| Nominal frequency AC [Hz]: | 45...65 |
| Protection class: | II |
| Reverse polarity protection: | yes |
| Total number of outputs: | 1 |
| Output function: | normally open |
| Max. voltage drop switching output DC [V]: | 7.5 |
| Minimum load current [mA]: | 6 |
| Max. leakage current [mA]: | 1.5 |
| Permanent current rating of switching output AC [mA]: | 200 |
| Permanent current rating of switching output DC [mA]: | 100 |
| Short-time current rating of switching output [mA]: | 2200; ((20 ms / 0,5 Hz)) |
| Short-circuit proof: | no |
| Overload protection: | no |
| Sensing range [mm]: | 10 |
| Sensing range adjustable: | no |
| Real sensing range Sr [mm]: | 10 ± 10 % |
| Operating distance [mm]: | 0...8.1 |
| Setting range [Imp/min]: | 5...3600 |
| Correction factor: | steel: 1 / stainless steel: 0.8 / brass: 0.5 / aluminium: 0.5 / copper: 0.4 |
| Hysteresis [% of Sr]: | 10 |
| Start-up delay [s]: | 12 |
| Max. damping frequency [Imp/min]: | 4800 |
| Adjustment of the switch point: | multiturn potentiometer |
| Ambient temperature [°C]: | -20...60 |
| Storage temperature [°C]: | -25...60 |
| Protection: | IP 65; IP 67 |
| Approval: | IECEx BVS 17.0094X |
| ATEX marking: | II 3D Ex tc IIIC T80°C Dc X |
| EMC: | EN 60947-5-2 |
| MTTF [years]: | 491 |
| Weight [K40]: | 314 |
| Mounting: | flush mountable |
| Dimensions [mm]: | M30 x 1.5 / L = 80 |
| Thread designation: | M30 x 1.5 |
| Materials: | brass special coating; PA; TPE-U |
| Display: | switching status 2 x LED, yellow |
| switching status: | 2 x LED, yellow |
| Required protection: | miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting; Place the fuse outside the hazardous area. |
| Accessories (supplied): | lock nuts: 2 |
| Remarks: | Recommendation Check the safe functioning of the unit after a short circuit. |
| Connection: | Cable: 2 m, PUR; 2 x 0.5 mm² |
| ECCN: | |
| Country of Origin: | DE |
| EAN: | |
| Weight: | 0.31 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |