Ifm DD2605

Evaluation unit for speed monitoring. MONITOR/FR-2N/110-240VAC/DC

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

For detecting frequency, speed and rotational speed. Monitoring of two input channels with one separate output relay each. Easy setting of the switch points via programming buttons. Clearly readable, luminous OLED display for programming and actual value indication. High input frequency of up to 60,000 pulses / minute

Technical parameters

Housing: housing for DIN rail mounting
Dimensions [mm]: 78 x 45 x 124.7
Application: pulse evaluation system with microprocessor for frequency; rotational speed; speed; pulses and machine cycles
Nominal voltage AC [V]: 110...240
Nominal voltage DC [V]: 27
Nominal voltage tolerance [%]: < 10
Nominal voltage tolerance 2 [%]: 20...10
Nominal frequency AC [Hz]: 50...60
Power consumption [W]: 3
Auxiliary energy for sensors DC [V]: 8.2
Number of inputs and outputs: Number of relay outputs: 2
Number of relay outputs: 2
Contact rating: 6 A (250 V AC); B300, R300
Setting range Hz [Hz]: 0.1...1000
Setting range [Imp/min]: 1...60000
Ambient temperature [°C]: -40...60
Storage temperature [°C]: -40...85
Max. relative air humidity [%]: 80; (40 °C: 50 %)
Protection: IP 50
Protection rating terminals: IP 20
EMC: EN 61010 2011 EMV 89/336/EWG EN 61000-6-2 : 2005 EN 61000-6-4 2007
EN 61010: 2011
EN 61000-6-2: : 2005
EN 61000-6-4: 2007
Weight [g]: 381.5
Housing: housing for DIN rail mounting
Dimensions [mm]: 78 x 45 x 124.7
Materials: plastics
Display: OLED display, 128 x 64 pixels luminous switching status LED, green
switching status: LED, green
Remarks: The unit complies with overvoltage category II; degree of soiling 2

Logistic parameters

ECCN:
Country of Origin: DE
EAN:
Weight: 0.38 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m