For the simple connection of binary sensors to any IO-Link master. Data and energy transmission also possible with unscreened connection cable. Clearly visible LEDs for displaying operation, switching status and error. Eight ports with two binary inputs each for sixteen sensors. Robust design with full potting for use in harsh industrial environments

Technical parameters

Operating voltage [V]: 18...30 DC; ("supply class 2" to cULus)
Current consumption [mA]: < 50
Current rating per port [A]: 0.1
Number of inputs and outputs: Number of digital inputs: 16
Number of digital inputs: 16; (8 x 2)
Input circuit of digital inputs: PNP
Sensor supply of the inputs: IO-Link
Input current limitation [mA]: 15
Input current High [mA]: 6...10
Input current Low [mA]: 0...2
Min. switching level high signal [V]: 11
Digital inputs protected against short circuits: yes
Communication interface: IO-Link
Transmission type: COM2 (38,4 kBaud)
IO-Link revision: 1.1
SDCI standard: IEC 61131-9
IO-Link device ID: 555d / 00 02 2Bh
SIO mode: no
Process data analogue: 1
Process data binary: 24
Min. process cycle time [ms]: 2.9
Ambient temperature [°C]: -25...70
Protection: IP 67
EMC: EN 61000-6-2 EN 61000-6-3 IEC 61131-9
MTTF [years]: 164
Weight [g]: 382.5
Materials: PA; socket: brass nickel-plated; O-ring: FKM
Display: operation LED, green errors LED, red function LED, yellow
operation: LED, green
errors: LED, red
function: LED, yellow
Accessories (optional): Stainless steel sleeve, for installation in case of high mechanical stress , E70402
Remarks: For use in NFPA 79 applications only The device is to be operated to IO-Link specification V1.1.2. The maximum cable length of the IO-Link cable is 20 m.
Pack quantity: 1 pcs.