AL1000
IO-Link master with PROFINET interface. IO-Link Master PL PN 8P IP67
Reliable transmission of machine data, process parameters and diagnostic data to the controller. For connection of up to eight IO-Link devices. With integrated fieldbus interface. Large operating temperature range and high protection rating. Robust housing for use in harsh industrial environments
Application: | I/O modules for field applications |
Daisy-chain function: | voltage supply; fieldbus interface |
Operating voltage [V]: | 19...31.2 DC; (US) |
Protection class: | III |
Additional voltage supply [V]: | 19...31.2 DC; (UA) |
Current rating per port [A]: | 1.6 |
Current rating per port [A]: | 0.2 |
Total number of inputs and outputs: | 12; (configurable) |
Number of inputs and outputs: | Number of digital inputs: 12; Number of digital outputs: 8 |
Number of digital inputs: | 12; (IO-Link Port Class A: 4 x 2; IO-Link Port Class B: 4 x 1) |
Switching level high [V]: | 15...30 |
Switching level low [V]: | -3...5 |
Digital inputs protected against short circuits: | yes |
Number of digital outputs: | 8; (IO-Link Port Class A: 4 x 1; IO-Link Port Class B: 4 x 1) |
Max. current load per output [mA]: | 200 |
Short-circuit proof: | yes |
Actuator supply switching outputs: | 24 V DC |
Communication interface: | Ethernet; IO-Link |
Protocol: | PROFINET |
Transmission type: | COM1 (4,8 kBaud); COM2 (38,4 kBaud); COM3 (230,4 kBaud) |
IO-Link revision: | 1.1 |
Number of ports class A: | 4 |
Number of ports class B: | 4 |
Ambient temperature [°C]: | -25...60 |
Storage temperature [°C]: | -25...85 |
Max. relative air humidity [%]: | 95 |
Protection: | IP 65; IP 67 |
EMC: | EN 61000-6-2 EN 61000-4-2 ESD 6 kV contact discharge / 8 kV air discharge EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 |
EN 61000-4-2 ESD: | 6 kV contact discharge / 8 kV air discharge |
Shock resistance: | EN 60068-2-27 30 g 11 ms |
EN 60068-2-27: | 30 g 11 ms |
Vibration resistance: | EN 60068-2-6 5 g |
EN 60068-2-6: | 5 g |
Weight [g]: | 574 |
Materials: | housing: PA; socket: brass nickel-plated |
Remarks: | For further information please see the operating instructions. |
Pack quantity: | 1 pcs. |
IN / OUT X21, X22: | Connector: M12 |
IO-Link Port Class A X01...X04: | Connector: M12 |
X31: | Connector: M12 |
X32: | Connector: M12 |
ECCN: | |
Country of Origin: | DE |
EAN: | |
Weight: | 0.57 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |