AC5292
AS-Interface ClassicLine module with quick mounting technology. ClassicLine 4DI-Y AUX 3DO-Y
Easy toolless installation and wiring thanks to quick mounting technology. Three freely selectable directions of the flat cable. Clearly visible powerful LEDs for displaying operation, switching status and error. High protection rating for the requirements of harsh industrial environments. Robust M12 connectors for connecting sensors and actuators
Operating voltage [V]: | 26.5...31.6 DC; ("supply class 2" to cULus) |
Max. current consumption from AS-i [mA]: | 30 |
Max. current load total [A]: | 3 |
Integrated watchdog: | yes |
Number of inputs and outputs: | Number of digital inputs: 4; Number of digital outputs: 3 |
Number of digital inputs: | 4 |
Input circuit of digital inputs: | PNP |
Sensor supply of the inputs: | AUX |
Voltage supply [V]: | 20...30; (via flat cable) |
Max. total current rating of inputs [mA]: | 1000 |
Input current High [mA]: | 6...10 |
Input current Low [mA]: | 0...2 |
Min. switching level high signal [V]: | 11 |
Digital inputs protected against short circuits: | yes |
Number of digital outputs: | 3 |
Circuit: | PNP |
Voltage range DC [V]: | 20...30; (to PELV; via flat cable) |
Max. current load per output [mA]: | 1000; (utilisation category DC-13 (control of electromagnets): 20 W (IEC 60947-5-1)) |
Short-circuit proof: | yes |
Electrically separated: | yes |
Ambient temperature [°C]: | -25...70 |
Protection: | IP 67 |
EMC: | EN 50295 IEC 61000-6-2 |
MTTF [years]: | 166 |
AS-i version: | 2.11; 3.0 |
AS-i addressing: | addressing socket |
Extended addressing mode possible: | yes |
AS-i profile: | S-7.A.E |
AS-i I/O configuration [hex]: | 7 |
AS-i ID code [hex]: | A.E |
AS-i certificate pending: | yes |
Assignment of the data bits: | data bit D0 D1 D2 D3 input 1 2 3 4 socket I-1/2 I-1/2 I-2 I-3/4 I-3/4 I-4 pin 4 2 4 4 2 4 Output 1 2 3 4 socket O-1/2 O-1/2 O2 O-3 - pin 4 2 4 4 - |
data bit: | D0 |
input: | 1 |
socket: | I-1/2 |
pin: | 4 |
Output: | 1 |
socket: | O-1/2 |
pin: | 4 |
Assignment of the parameter bits: | parameter bit Designation P0 not used P1 peripheral fault indication : 1 activated * / 0 deactivated P2 not used P3 not used |
parameter bit: | Designation |
P0: | not used |
P1: | peripheral fault indication |
P2: | not used |
P3: | not used |
Weight [g]: | 289.5 |
Type of mounting: | AS-i flat cables directly connectable |
Materials: | PA; piercing contacts: CuSn6 nickel-plated and tin-plated |
Display: | operation LED, green Voltage AUX > 7 V errors LED, red AUX 15 V ± 2 V function LED, yellow |
operation: | LED, green Voltage AUX > 7 V |
errors: | LED, red AUX 15 V ± 2 V |
function: | LED, yellow |
Accessories (supplied): | lower part |
Accessories (optional): | Protective cap: M12, E73004 |
Pack quantity: | 1 pcs. |
Connection: | Connector: M12 |
Connection: | Connector: M12 |
ECCN: | |
Country of Origin: | DE |
EAN: | |
Weight: | 0.29 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |