AC5227
AS-Interface Airbox with quick mounting technology. AirBox 2x3/2 2DI IP67
For the decentralised triggering of cylinders and valve actuators. Combination of AS-i I/O module and solenoid valve. High energy efficiency due to decentralised application near the actuator. Reduced installation and wiring complexity. Easy toolless installation and wiring thanks to quick mounting technology
| Medium temperature [°C]: | -10...50 |
| Operating voltage [V]: | 26.5...31.6 DC |
| Max. current consumption from AS-i [mA]: | 180 |
| Integrated watchdog: | yes |
| Number of inputs and outputs: | Number of digital inputs: 2; Number of pneumatic outputs: 2 |
| Number of digital inputs: | 2 |
| Input circuit of digital inputs: | PNP |
| Sensor supply of the inputs: | AS-i |
| Voltage supply [V]: | 20...30; (via flat cable) |
| Max. total current rating of inputs [mA]: | 100 |
| Input current High [mA]: | 6...10 |
| Input current Low [mA]: | 0...2 |
| Min. switching level high signal [V]: | 11 |
| Digital inputs protected against short circuits: | yes |
| Electrical design: | AS-i |
| Number of pneumatic outputs: | 2 |
| Ambient temperature [°C]: | -10...55 |
| Protection: | IP 67 |
| EMC: | EN 50295 IEC 61000-6-2 |
| MTTF [years]: | 321 |
| AS-i version: | 2.11; 3.0 |
| AS-i addressing: | addressing socket |
| Extended addressing mode possible: | no |
| AS-i profile: | S-3.F.F |
| AS-i I/O configuration [hex]: | 3 |
| AS-i ID code [hex]: | F.F |
| AS-i certificate pending: | yes |
| Assignment of the data bits: | data bit D0 D1 D2 D3 input 1 2 3 4 socket I-1 I-2 - - pin 2+4 2+4 - - pneumatic output - - 2 4 |
| data bit: | D0 |
| input: | 1 |
| socket: | I-1 |
| pin: | 2+4 |
| pneumatic output: | - |
| Weight [g]: | 378.5 |
| Type of mounting: | AS-i flat cables directly connectable |
| Materials: | PA; POM; piercing contacts: CuSn6 nickel-plated and tin-plated |
| Pneumatic system: | 2 x 3/2-way slide valves (free from overlapping) |
| Operating pressure range [bar]: | 2...8 |
| Operating pressure range [MPa]: | 0.2...0.8 |
| Operating pressure range [psi]: | 29...116 |
| Air flow at 6/5 bar [l/min]: | 500 |
| Permissible compressed air: | non-lubricated compressed air class 6-3-1; lubricated compressed air class 6-3-4 |
| Manual override: | pressing/releasing or pressing/turning/locking |
| Tube fittings: | 8 mm |
| Exhaust: | exhaust can be discharged through tube connection |
| Display: | operation LED, green errors LED, red function LED, yellow |
| operation: | LED, green |
| errors: | LED, red |
| function: | LED, yellow |
| Accessories (supplied): | lower part |
| Accessories (optional): | Mounting plate:, E74999 Module lower part:, E75000 Protective cap: M12, E73004 sealing plugs:, E75231 silencer:, E75232 Push-in L-fitting:, E75228 Push-in T-fitting:, E75227 |
| Remarks: | If not pneumatically operated, E75231 sealing plug must be inserted. Avoid ingress of dirt and dust. Do not connect any of the following points to an external potential: L-, L+, I-1, I-2 The connections are electrically connected with the AS-i cable. Notes on compressed air and EMC/ESD at www.ifm.com |
| Pack quantity: | 1 pcs. |
| ECCN: | |
| Country of Origin: | DE |
| EAN: | |
| Weight: | 0.38 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |