Description

Easy toolless installation and wiring thanks to quick mounting technology. Three freely selectable directions of the flat cable. Clearly visible powerful LEDs for displaying operation, switching status and error. High protection rating for the requirements of harsh industrial environments. Robust M12 connectors for connecting sensors and actuators

Technical parameters

Number of inputs and outputs: Number of analogue inputs: 4
Operating voltage [V]: 18...31.6 DC; ("supply class 2" to cULus)
Max. current consumption from AS-i [mA]: 50
Reverse polarity protection: yes
Max. current load total [A]: 2
Additional voltage supply [V]: 16...30 DC; (AUX)
Number of inputs and outputs: Number of analogue inputs: 4
Number of analogue inputs: 4; (Anschluss von 2-, 3-, 4-Draht-Sensoren)
Sensor supply of the inputs: AUX
Analogue input (current) [mA]: 4...20
Max. voltage drop across load for nominal voltage [V]: 10
Analogue inputs protected against short circuits: yes
Resolution of analogue input: 12 bit
Measuring error [% of the final value]: 0,5 *)
Ambient temperature [°C]: -25...70
Protection: IP 67
EMC: EN 50295 EN 61000-6-2 EN 61000-6-3
MTTF [years]: 105
AS-i version: 2.11; 3.0
Extended addressing mode possible: no
AS-i profile: S-7.3.E
AS-i I/O configuration [hex]: 7
AS-i ID code [hex]: 3.E
AS-i certificate: 123501
Weight [g]: 188
Type of mounting: AS-i flat cables directly connectable
Materials: PA; piercing contacts: CuSn6 nickel-plated and tin-plated
Display: operation LED, green Voltage AS-i errors LED, red function LED, yellow channels AI1...AI4
operation: LED, green Voltage AS-i
errors: LED, red
function: LED, yellow channels AI1...AI4
Accessories (supplied): lower part
Accessories (optional): Protective cap: M12, E73004
Remarks: There is an electrical separation between AS-i and AUX and between AS-i and the analogue inputs. The actuator supply on pins 1 and 3 can be used to supply the sensors. 3-wire connection possible via external link.
Pack quantity: 1 pcs.

Logistic parameters

ECCN:
Country of Origin: DE
EAN:
Weight: 0.19 kg