AC5226
AS-Interface ClassicLine module with quick mounting technology. ClassicLine 4AI C AUX IP67
Easy toolless installation and wiring thanks to quick mounting technology. Three freely selectable directions of the flat cable. Clearly visible powerful LEDs for displaying operation, switching status and error. High protection rating for the requirements of harsh industrial environments. Robust M12 connectors for connecting sensors and actuators
Number of inputs and outputs: | Number of analogue inputs: 4 |
Operating voltage [V]: | 18...31.6 DC; ("supply class 2" to cULus) |
Max. current consumption from AS-i [mA]: | 50 |
Reverse polarity protection: | yes |
Max. current load total [A]: | 2 |
Additional voltage supply [V]: | 16...30 DC; (AUX) |
Number of inputs and outputs: | Number of analogue inputs: 4 |
Number of analogue inputs: | 4; (Anschluss von 2-, 3-, 4-Draht-Sensoren) |
Sensor supply of the inputs: | AUX |
Analogue input (current) [mA]: | 4...20 |
Max. voltage drop across load for nominal voltage [V]: | 10 |
Analogue inputs protected against short circuits: | yes |
Resolution of analogue input: | 12 bit |
Measuring error [% of the final value]: | 0,5 *) |
Ambient temperature [°C]: | -25...70 |
Protection: | IP 67 |
EMC: | EN 50295 EN 61000-6-2 EN 61000-6-3 |
MTTF [years]: | 105 |
AS-i version: | 2.11; 3.0 |
Extended addressing mode possible: | no |
AS-i profile: | S-7.3.E |
AS-i I/O configuration [hex]: | 7 |
AS-i ID code [hex]: | 3.E |
AS-i certificate: | 123501 |
Weight [g]: | 188 |
Type of mounting: | AS-i flat cables directly connectable |
Materials: | PA; piercing contacts: CuSn6 nickel-plated and tin-plated |
Display: | operation LED, green Voltage AS-i errors LED, red function LED, yellow channels AI1...AI4 |
operation: | LED, green Voltage AS-i |
errors: | LED, red |
function: | LED, yellow channels AI1...AI4 |
Accessories (supplied): | lower part |
Accessories (optional): | Protective cap: M12, E73004 |
Remarks: | There is an electrical separation between AS-i and AUX and between AS-i and the analogue inputs. The actuator supply on pins 1 and 3 can be used to supply the sensors. 3-wire connection possible via external link. |
Pack quantity: | 1 pcs. |
ECCN: | |
Country of Origin: | DE |
EAN: | |
Weight: | 0.19 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |