AC2910
AS-Interface ProcessLine module. ProcessLine 8DI IP69K
Specially for the use in wet areas of the food and beverage industry. Hygienic design without corners and edges. Resistant to high-pressure cleaning with aggressive cleaning agents. Clearly visible powerful LEDs for displaying operation, switching status and error
| Operating voltage [V]: | 26.5...31.6 DC |
| Max. current consumption from AS-i [mA]: | 500 |
| Number of inputs and outputs: | Number of digital inputs: 8 |
| Number of digital inputs: | 8; (2 x Slave) |
| Input circuit of digital inputs: | PNP; (type 2 according to IEC 61131-2 ) |
| Sensor supply of the inputs: | AS-i |
| Voltage supply [V]: | 18...30; (DC) |
| Max. total current rating of inputs [mA]: | 400 |
| Input current High [mA]: | 6...10 |
| Input current Low [mA]: | 0...2 |
| Min. switching level high signal [V]: | 11 |
| Digital inputs protected against short circuits: | yes |
| Ambient temperature [°C]: | -5...70 |
| Protection: | IP 68; IP 69K |
| EMC: | EN 62026-2 EN 61000-6-2 |
| MTTF [years]: | 212 |
| AS-i version: | 2.1 |
| Extended addressing mode possible: | yes |
| AS-i profile: | S-0.A.E |
| AS-i I/O configuration [hex]: | 0 |
| AS-i ID code [hex]: | A.E |
| AS-i certificate: | 88901 |
| Assignment of the data bits: | data bit D0 D1 D2 D3 input 1 2 3 4 socket I-1/2 I-1/2 I-2 I-3/4 I-3/4 I-4 pin 4 2 4 4 2 4 |
| data bit: | D0 |
| input: | 1 |
| socket: | I-1/2 |
| pin: | 4 |
| Weight [g]: | 643 |
| Dimensions [mm]: | 137.3 x 80 x 137.3 |
| Materials: | threaded bush : stainless steel (1.4404 / 316L) ; PC; O-ring: EPDM |
| Display: | operation LED, green errors LED, red function LED, yellow |
| operation: | LED, green |
| errors: | LED, red |
| function: | LED, yellow |
| Accessories (supplied): | Protective cap: M12, E70297 |
| Accessories (optional): | Torque wrench:, E70390 Flat cable insulation displacement connector:, E70454 Flat cable insulation displacement connector :, E70354 |
| Remarks: | Inputs and outputs must be electrically isolated. Do not connect any of the following points to an external potential: I-, I+, I-1/2, I-2, I-3/4, I-4 The connections are electrically connected with the AS-i cable. default setting of the ID1 codes: slave 1=1 / slave 2=2 The round cable connected to AS-i should not be longer than 2 m. |
| Pack quantity: | 1 pcs. |
| Connection: | Connector: M12 |
| ECCN: | |
| Country of Origin: | DE |
| EAN: | |
| Weight: | 0.64 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |