AC2731
AS-Interface PCB module. PCB 3DI 3DO T IP00
For installation in small housings, control cabinets and operator panels. Simple and fast wiring by means of screw terminals. Particularly space-saving design. For integration of mechanical switches into AS-i networks. AS-i connection for three control and signalling devices
Operating voltage [V]: | 26.5...31.6 DC |
Current consumption [mA]: | < 200 |
Max. current load total [A]: | 0.18 |
Integrated watchdog: | yes |
Number of inputs and outputs: | Number of digital inputs: 3; Number of digital outputs: 3 |
Number of digital inputs: | 3 |
Sensor supply of the inputs: | AS-i |
Voltage supply [V]: | 20...30 |
Digital inputs protected against short circuits: | yes |
Number of digital outputs: | 3 |
Voltage range DC [V]: | AS-i |
Max. current load per output [mA]: | 180; (note current load for all inputs and outputs ) |
Short-circuit proof: | yes |
Ambient temperature [°C]: | -25...70 |
Protection: | IP 00 |
EMC: | EN 50295 |
AS-i version: | 2.1 |
Extended addressing mode possible: | yes |
AS-i profile: | S-7.A.E |
AS-i I/O configuration [hex]: | 7 |
AS-i ID code [hex]: | A.E |
Assignment of the data bits: | data bit D0 D1 D2 D3 input I-1 I-2 I-3 - Output O-1 O-2 O-3 - |
data bit: | D0 |
input: | I-1 |
Output: | O-1 |
Weight [g]: | 30.5 |
Display: | operation LED, green failure LED, red |
operation: | LED, green |
failure: | LED, red |
Remarks: | The AS-i module is a PCB solution for an AS-i slave, supply via AS-i. A watchdog function switches the outputs off if there is no communication on the AS-i line. |
Pack quantity: | 1 pcs. |
ECCN: | |
Country of Origin: | DE |
EAN: | |
Weight: | 0.03 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |