Ifm AC2709

AS-Interface control cabinet module. CabinetModule 4DI 4DO T W

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

For installation in small housings, control cabinets and operator panels. Simple and fast wiring by means of wire strands. Particularly space-saving design. For integration of mechanical switches into AS-i networks. AS-i connection for four control and signalling devices

Technical parameters

Operating voltage [V]: 26.5...31.6 DC
Current consumption [mA]: < 250
Max. current load total [A]: 0.2
Number of inputs and outputs: Number of digital inputs: 4; Number of digital outputs: 4
Number of digital inputs: 4
Input circuit of digital inputs: PNP
Sensor supply of the inputs: AS-i
Voltage supply [V]: 15...29
Input current High [mA]: > 3
Input current Low [mA]: < 1.5
Min. switching level high signal [V]: 10
Digital inputs protected against short circuits: yes
Number of digital outputs: 4
Circuit: PNP
Max. current load per output [mA]: 50
Short-circuit proof: yes
Electrically separated: yes
Ambient temperature [°C]: -25...60
Protection: IP 20
EMC: EN 50295
MTTF [years]: 322
AS-i version: 2.1
Extended addressing mode possible: no
AS-i profile: S-7.0.F
AS-i I/O configuration [hex]: 7
AS-i ID code [hex]: 0.F
AS-i certificate pending: yes
Weight [g]: 115
Type of mounting: for Moeller housing RMQ-Titan: I3M, I4M, I6M
Display: operation LED, green
operation: LED, green
Remarks: The PCB can also be integrated into an RMQ22 housing. Do not connect any of the following points to an external potential: O-, I+, I1, I2, I3, I4 The connections are electrically connected with the AS-i cable. Install the unit so that exposed parts cannot be touched.
Pack quantity: 1 pcs.

Logistic parameters

ECCN:
Country of Origin: DE
EAN:
Weight: 0.12 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m