AC2709
AS-Interface control cabinet module. CabinetModule 4DI 4DO T W
For installation in small housings, control cabinets and operator panels. Simple and fast wiring by means of wire strands. Particularly space-saving design. For integration of mechanical switches into AS-i networks. AS-i connection for four control and signalling devices
Operating voltage [V]: | 26.5...31.6 DC |
Current consumption [mA]: | < 250 |
Max. current load total [A]: | 0.2 |
Number of inputs and outputs: | Number of digital inputs: 4; Number of digital outputs: 4 |
Number of digital inputs: | 4 |
Input circuit of digital inputs: | PNP |
Sensor supply of the inputs: | AS-i |
Voltage supply [V]: | 15...29 |
Input current High [mA]: | > 3 |
Input current Low [mA]: | < 1.5 |
Min. switching level high signal [V]: | 10 |
Digital inputs protected against short circuits: | yes |
Number of digital outputs: | 4 |
Circuit: | PNP |
Max. current load per output [mA]: | 50 |
Short-circuit proof: | yes |
Electrically separated: | yes |
Ambient temperature [°C]: | -25...60 |
Protection: | IP 20 |
EMC: | EN 50295 |
MTTF [years]: | 322 |
AS-i version: | 2.1 |
Extended addressing mode possible: | no |
AS-i profile: | S-7.0.F |
AS-i I/O configuration [hex]: | 7 |
AS-i ID code [hex]: | 0.F |
AS-i certificate pending: | yes |
Weight [g]: | 115 |
Type of mounting: | for Moeller housing RMQ-Titan: I3M, I4M, I6M |
Display: | operation LED, green |
operation: | LED, green |
Remarks: | The PCB can also be integrated into an RMQ22 housing. Do not connect any of the following points to an external potential: O-, I+, I1, I2, I3, I4 The connections are electrically connected with the AS-i cable. Install the unit so that exposed parts cannot be touched. |
Pack quantity: | 1 pcs. |
ECCN: | |
Country of Origin: | DE |
EAN: | |
Weight: | 0.12 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |