Ifm AC2508

ClassicLine45 4DO T M12

AS-Interface ClassicLine module. ClassicLine45 4DO T M12

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

Technical parameters

Operating voltage [V]: 26.5...31.6 DC
Max. current consumption from AS-i [mA]: 50
Max. current load total [A]: 2
Integrated watchdog: yes
Number of inputs and outputs: Number of digital outputs: 4
Electrical design: AS-i
Number of digital outputs: 4
Circuit: PNP
Voltage range DC [V]: 15...30; (to PELV; via flat cable; for cULus the voltage must comply with the values specified in "Limited Voltage/Current")
Max. current load per output [mA]: 1000; (utilisation category DC-13 (control of electromagnets): 20 W (IEC 60947-5-1); according to cULus: 700 mA)
Short-circuit proof: yes
Electrically separated: yes
Ambient temperature [°C]: -25...70
Protection: IP 67
EMC: EN 50295
MTTF [years]: 255
AS-i version: 2.1
AS-i addressing: IR addressing possible
Extended addressing mode possible: no
AS-i profile: S-8.0.E
AS-i I/O configuration [hex]: 8
AS-i ID code [hex]: 0.E
AS-i certificate: 39201
Assignment of the data bits: data bit D0 D1 D2 D3 Output 1 2 3 4 socket O-1 O-2 O-3 O-4 pin 4 4 4 4
data bit: D0
Output: 1
socket: O-1
pin: 4
Weight [g]: 109
Type of mounting: AS-i interface to FC-E lower parts
Materials: PBT
Display: operation LED, green errors LED, red function LED, yellow
operation: LED, green
errors: LED, red
function: LED, yellow
Accessories (optional): Module lower part
Notes: discontinued article
Pack quantity: 1 pcs.

Logistic parameters

ECCN:
Country of Origin: DEUTSCHLAND
EAN:
Weight: 0.11 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m