AS-Interface power supply. PSU-3AC/ASi-8A
Reliably power supply for modules, sensors and actuators. High noise immunity and sufficient power reserves for the compensation of current peaks. Safe decoupling of interferences from the primary supply. Particularly space-saving design. Low heating of the control cabinet due to high efficiency
Frequency AC [Hz]: | 47...64 |
Operating voltage tolerance [%]: | 15...20 |
Nominal voltage AC [V]: | 400 |
Input voltage range AC [V]: | 380...480 |
Protection class: | I |
Overvoltage protection: | yes; (< 36 V) |
Max. power-on delay time [ms]: | 90 |
Output voltage AS-i [V]: | 30.5 |
Output power (permanent) [W]: | 244 |
Output power (peak) [W]: | 256 |
Note on output power (peak): | briefly to load bus capacities after power on |
Power factor (nominal voltage 400 V AC / 50 Hz): | 0.53 |
Power factor (nominal voltage 480 V AC / 50 Hz): | 0.52 |
Power reserve [%]: | 5 |
Number of output circuits: | 1 |
Output current AS-i [A]: | 8 |
Max. residual ripple [mV]: | 90 |
Switch-on peak current (nominal voltage 400 V AC / 60 Hz) [A]: | 4 |
Switch-on peak current (nominal voltage 480 V AC / 50 Hz) [A]: | 4 |
Efficiency (nominal voltage 400 V AC / 60 Hz) [%]: | 92 |
Efficiency (nominal voltage 480 V AC / 50 Hz) [%]: | 92.1 |
External input protection: | ≤ B-6 A / ≤ C-3 A |
Derating [W/K]: | 6 (60...70 °C) |
Mains buffering time (nominal voltage 400 V AC / 60 Hz) [ms]: | 34 |
Mains buffering time (nominal voltage 480 V AC / 50 Hz) [ms]: | 53 |
Input current (nominal voltage 400 V AC / 60 Hz) [A]: | 0.7 |
Input current (nominal voltage 480 V AC / 50 Hz) [A]: | 0.6 |
Power loss (nominal voltage 400 V AC / 60 Hz) [W]: | 21.2 |
Power loss (nominal voltage 480 V AC / 50 Hz) [W]: | 20.9 |
Integrated data decoupling: | yes |
Back feeding protection [V]: | 35 |
Short-circuit proof: | yes |
Overload protection: | yes |
Overload performance: | output current constant |
Parallel connection of outputs possible: | no |
Series connection of outputs possible: | no |
Ambient temperature [°C]: | -25...70 |
Note on ambient temperature: | observe the free space for convection (see operating instructions) |
Storage temperature [°C]: | -40...85 |
Max. relative air humidity [%]: | 95; (IEC 60068-2-30) |
Protection: | IP 20 |
Degree of soiling: | 2; (IEC 62103: conductive soiling not permitted) |
EMC: | EN 61000-6-1 EN 61000-6-2 EN 61000-6-3 EN 61000-6-4 |
Vibration resistance: | IEC 60068-2-6 ± 1,6 mm 2...17,8 Hz / 2 g 17,8...500 Hz |
IEC 60068-2-6: | ± 1,6 mm 2...17,8 Hz / 2 g 17,8...500 Hz |
Shock resistance: | IEC 60068-2-27 30 g 6 ms / 20 g 11 ms |
IEC 60068-2-27: | 30 g 6 ms / 20 g 11 ms |
Power Factor Correction (PFC): | met |
AS-i certificate: | 98401 |
Weight [K40]: | 948.5 |
Type of mounting: | rail; (TH35 (EN 60715)) |
Dimensions [mm]: | 124 x 62 x 120 |
Materials: | steel sheet |
Display: | AS-i voltage LED, green |
AS-i voltage: | LED, green |
Pack quantity: | 1 pcs. |
Connection: | screw terminals: |
ECCN: | |
Country of Origin: | CN |
EAN: | |
Weight: | 0.95 kg |
Length: | 0.00 m |
Width: | 0.00 m |
Height: | 0.00 m |