Ifm AC031S

Safety mon/1 ch. enhan. net

AS-Interface safety monitor. Safety mon/1 ch. enhan. net

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

Technical parameters

Operating voltage tolerance [%]: 15
Operating voltage [V]: 24 DC
Max. current consumption from AS-i [mA]: 45
Switch-on peak current [mA]: 600
Transmission rate: 9600 Baud
Ambient temperature [°C]: -20...60
Storage temperature [°C]: -30...70
Protection: IP 20; (Only suitable for use in electrical operating rooms or control cabinets with minimum protection rating IP54.)
EMC: EN 50081-2 (1993) EN 61000-6-2 (1999) EN 60947-5-1 (2000) EN 60204-1
EN 50081-2: (1993)
EN 61000-6-2: (1999)
EN 60947-5-1: (2000)
ISO 13849-1: PL e
IEC 61508: SIL 3
Mission time TM [h]: 175200
Mission time TM (additional indication): 20 years
AS-i profile: 7.F
AS-i I/O configuration [hex]: 7
AS-i ID code [hex]: F
AS-i certificate pending: yes
Weight [g]: 384
Materials: PA black
Notes: discontinued article
Pack quantity: 1 pcs.

Logistic parameters

ECCN:
Country of Origin: DEUTSCHLAND
EAN:
Weight: 0.38 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m