ELX3202-0090
ELX3202-0090 | 2-channel analog input terminal RTD for 2, 3 and 4-wire connection, 16 bit, Ex i, TwinSAFE SC
The ELX3202-0090 analog input terminal allows the direct connection of RTDs located in hazardous areas classified Zone 0/20 or 1/21. The circuitry of the ELX3202-0090 can operate sensors with 2, 3 and 4-wire technology. Linearisation is carried out over the entire freely selectable temperature range. By default the terminal is set to PT100 sensors with 3-wire technology. The ELX3202-0090 terminal indicates signal state and sensor malfunctions (e.g. wire breakage) by means of LEDs.
| Number of inputs: | 2 (differential) | 
| Power supply: | via the E-bus | 
| Connection method: | 2-, 3-, 4-wire (default: 2-wire) | 
| Temperature range: | -200…+850 °C (PT sensors); -60…+250 °C (Ni sensors), for further types and details see documentation | 
| Resolution: | up to 0.01 °C per digit (preset: 0.1 °C per digit) | 
| Measuring current: | < 1 mA (depending on sensor and measuring range) | 
| Measuring error: | < ±0.3 % (relative to full scale value) | 
| Internal resistance: | typ. ≥ 10 kΩ (differential) | 
| Input filter limit frequency: | typ. 1 kHz | 
| Sensor types: | PT100, PT200, PT500, PT1000, Ni100, Ni120, Ni1000 resistance measurement (10 Ω…4 kΩ), KT(Y) sensors | 
| Conversion time: | 10…3300 ms (adjustable, default: 270 ms) | 
| Supply voltage electronics: | 24 V DC (via power contacts), ELX9560 power supply | 
| Current consumption power contacts: | typ. 10 mA | 
| Current consumption E-bus: | typ. 70 mA | 
| Special features: | limit value monitoring, digital filter and characteristic curve linearisation integrated, connection method freely configurable, TwinSAFE SC | 
| Weight: | approx. 60 g | 
| Operating/storage temperature: | -25…+60 °C/-40…+85 °C | 
| Relative humidity: | 95 %, no condensation | 
| Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 | 
| EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 | 
| Protect. class/installation pos.: | IP 20/see documentation | 
| Approvals/markings: | CE, UL, ATEX, IECEx, cFMus | 
| Ex marking: | ATEX: II 3(1)G Ex ec [ia Ga] IIC T4 Gc II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I IECEx: Ex ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I cFMus: AIS Class I, II, III, Division 1, Groups A thru G Class I, Division 2, Groups A, B, C, D Class I, Zone 2, AEx nA [ia Ga] IIC T4 Gc Class I, Zone 2, AEx ec [ia Ga] IIC T4 Gc [AEx ia Da] IIIC T4 | 
| ECCN: | |
| Country of Origin: | |
| EAN: | |
| Weight: | 0.00 kg | 
| Length: | 0.00 m | 
| Width: | 0.00 m | 
| Height: | 0.00 m |