ELM9410
ELM9410 | Power supply terminal for refreshing the E-bus, with diagnostics
The ELM9410 power supply terminal is used to increase the E-bus current. The exchange of data between EtherCAT Couplers and the connected EtherCAT Terminals takes place over the E-bus. Each EtherCAT Terminal requires a certain amount of current from the E-bus (see technical data at the respective terminal: “Current consumption E-bus“). This current is fed into the E-bus by the power supply unit of the respective EtherCAT Coupler. In configurations with a large number of EtherCAT Terminals, the ELM9410 can be used to increase the current supply to the E-bus by 2 A.
| Technology: | power supply terminal |
| Short-circuit proof: | yes |
| Input voltage: | 24 V DC |
| Input current: | typ. 70 mA + (E-bus/4) |
| Power supply: | 24 V DC (-15 %/+20 %) |
| Output voltage: | 5 V for E-bus supply |
| Output current: | 2 A |
| Current consumption E-bus: | – |
| Current consumption from US: | 50 mA + (∑ E-bus current/4) |
| Current consumption from UP: | 50 mA + load |
| Current supply E-bus: | 2000 mA |
| Insulation voltage input/output: | 500 V (E-bus/US/UP) |
| Power contacts: | max. 24 V DC/max. 2 A |
| Diagnostics in the process image: | yes |
| Special features: | electrically isolated output voltages, reverse polarity protection, diagnostics of supply and output voltages |
| Weight: | approx. 450 g |
| Operating/storage temperature: | 0…+60 °C/-25…+85 °C |
| Relative humidity: | 95 %, no condensation |
| Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
| Electrical isolation: | 500 V (E-bus/field potential) |
| EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos.: | IP 20/variable |
| Approvals/markings: | CE |
| ECCN: | |
| Country of Origin: | |
| EAN: | |
| Weight: | 0.00 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |