EL9400
EL9400 | Power supply terminal for E-bus
The EL9400 power supply terminal is used to refresh the E-bus. Data is exchanged between the coupler and the EtherCAT Terminal over the E-bus. Each terminal draws a certain amount of current from the E-bus (see “current consumption E-bus” in the technical data). This current is fed into the E-bus by the relevant coupler’s power supply unit. In configurations with a large number of terminals it is possible to use the EL9400 in order to supply an extra 2 A to the E-bus.
| Technology: | power supply terminal |
| Short-circuit proof: | – |
| Input voltage: | 24 V DC (-15 %/+20 %) |
| Input current: | typ. 70 mA + (E-bus/4) |
| Output voltage: | 5 V for E-bus supply |
| Output current: | 2 A |
| Current consumption E-bus: | – |
| Electrical isolation: | 500 V (E-bus/field potential) |
| Insulation voltage input/output: | – |
| Power contacts: | max. 24 V DC/max. 10 A |
| Diagnostics in the process image: | – |
| Special features: | for new projects: please use EL9410 |
| Weight: | approx. 65 g |
| Operating/storage temperature: | 0…+55 °C/-25…+85 °C |
| Relative humidity: | 95 %, no condensation |
| Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos.: | IP 20/variable |
| Pluggable wiring: | for all ESxxxx terminals |
| Approvals: | CE, UL, Ex |
| ECCN: | |
| Country of Origin: | |
| EAN: | |
| Weight: | 0.00 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |