EL2732
EL2732 | 2-channel triac output terminal
The EL2732 output terminal uses a power switch to control mains voltage from 12 V to 230 V AC. The switching element is a triac, which is connected to the power contact potential. As a semiconductor switch, it is not subject to wear. The steady load capacity of a digital output is 1 A. The EtherCAT Terminal has two independent outputs and indicates its signal state by means of light emitting diodes.
| Connection technology: | triac output, 2-wire | 
| Number of outputs: | 2 x make contacts (without power contacts), mutually locked | 
| Rated load voltage: | 12…230 V AC | 
| Load type: | ohmic, inductive | 
| Distributed clocks: | – | 
| Max. output current: | 0.5 A | 
| Switching times: | in zero crossing, 0.1…10 ms | 
| Frequency range: | 47…63 Hz | 
| Surge voltage protection: | > 275 V | 
| Peak current: | 40 A (16 ms), 1.5 A (30 s) | 
| Standby current: | 0.6 mA | 
| Leakage current (OFF state): | typ. 0.8 mA, max. 1.5 mA | 
| Switch-on time: | 0.1…10 ms, zero crossing | 
| Switch-off time: | T/2 | 
| Max. residual voltage: | 1.5 V (60 mA…1 A), 150 Ω (< 60 mA) | 
| Current consumption E-bus: | typ. 120 mA | 
| Electrical isolation: | 500 V (E-bus/field voltage), 3750 V AC (1 min.) | 
| Current consumption power contacts: | – | 
| Bit width in the process image: | 2 outputs | 
| Configuration: | no address or configuration setting | 
| Special features: | suitable for conventional blind motors | 
| Weight: | approx. 55 g | 
| Operating/storage temperature: | 0…+55 °C/-25…+85 °C | 
| Relative humidity: | 95 %, no condensation | 
| Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 | 
| EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 | 
| Protect. class/installation pos.: | IP 20/variable | 
| Pluggable wiring: | for all ESxxxx terminals | 
| ECCN: | |
| Country of Origin: | |
| EAN: | |
| Weight: | 0.00 kg | 
| Length: | 0.00 m | 
| Width: | 0.00 m | 
| Height: | 0.00 m |