EL2624 | 4-channel relay output terminal 125 V AC/30 V DC
The EL2624 output terminal has four relays each of which has a single contact. The relay contact is suitable for use at up to 125 V AC or 30 V DC. The EtherCAT Terminal indicates its signal state by means of light emitting diodes. The EL2624 has potential-free contacts. The power contacts are looped through.
| Connection technology: | relay output |
| Number of outputs: | 4 x make contacts |
| Nominal voltage: | 125 V AC/30 V DC |
| Load type: | ohmic |
| Distributed clocks: | – |
| Ohmic switching current: | 0.5 A AC/2 A DC per channel |
| Inductive switching current: | no data |
| Minimum permitted load: | 10 µA at 10 mV DC with intact contact coating |
| Current consumption E-bus: | typ. 200 mA |
| Electrical isolation: | 500 V (E-bus/field potential) |
| Current consumption power contacts: | – |
| Bit width in the process image: | 4 outputs |
| Operating cycles mech. (min.): | 1 x 108 |
| Operating cycles electr. (min.): | 2 x 105 (1 A/30 V DC) |
| Configuration: | no address or configuration setting |
| Weight: | approx. 50 g |
| Operating/storage temperature: | 0…+55 °C/-25…+85 °C |
| Relative humidity: | 95 %, no condensation |
| Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos.: | IP 20/variable |
| Pluggable wiring: | for all ESxxxx terminals |
| Approvals: | CE, UL |