EL2212
EL2212 | 2-channel digital output terminal 24…72 V DC with overexcitation, multi-timestamping
The EL2212 digital output terminal connects the binary control signals from the automation unit on to the actuators at the process level with electrical isolation. With multi-timestamping as many events can be read per channel in each EtherCAT cycle, as were pre-loaded in the internal buffer.
| Connection technology: | 4-wire |
| Number of outputs: | 2 |
| Nominal voltage: | 24…72 V DC (-15 %/+0 %) |
| Load type: | inductive > 1 mH |
| Precision of timestamp in the terminal: | 10 ns |
| Resolution timestamp: | 1 ns |
| Distributed clocks: | yes |
| Distributed clock precision: | << 1 µs |
| Max. output current: | peak current: max. 10 A per channel, holding current: 0.2…2.5 A per channel |
| Output stage: | full bridge (push-pull) |
| Short-circuit current: | typ. 12 A |
| Reverse voltage protection: | – |
| Switching times: | without distributed clocks: typ. TON/TOFF 20 µs, with distributed clocks: typ. TON/TOFF < 1 µs via internal compensation |
| Current consumption E-bus: | typ. 120 mA |
| Electrical isolation: | 500 V (E-bus/field potential) |
| Current consumption power contacts: | load-dependent |
| Configuration: | via TwinCAT System Manager |
| Special features: | Multi-timestamping, current-controlled outputs can be connected in high-resistance mode. |
| Weight: | approx. 50 g |
| Operating/storage temperature: | 0…+55 °C/-25…+85 °C |
| Relative humidity: | 95 %, no condensation |
| Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos.: | IP 20/variable |
| Pluggable wiring: | for all ESxxxx terminals |
| Approvals/markings: | CE |
| ECCN: | |
| Country of Origin: | |
| EAN: | |
| Weight: | 0.00 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |