EL2034
EL2034 | 4-channel digital output terminal 24 V DC, 2 A
The EL2034 digital output terminal connects the binary 24 V control signals, electrically isolated, with the actuators. Four channels are available and indicate their signal state via LEDs. The terminal enables direct connection of four 2-wire actuators. They feature four earth connecting points. The EL2034 offers output diagnostics in the form of short circuit and open circuit detection per channel.
| Connection technology: | 2-wire |
| Number of outputs: | 4 |
| Rated load voltage: | 24 V DC (-15 %/+20 %) |
| Load type: | ohmic, inductive, lamp load |
| Distributed clocks: | – |
| Max. output current: | 2.0 A (short-circuit-proof) per channel, with diagnostics |
| Short circuit current: | typ. < 70 A |
| Reverse voltage protection: | yes |
| Breaking energy: | < 1.7 J/channel |
| Switching times: | typ. TON: 40 µs, typ. TOFF: 200 µs |
| Current consumption E-bus: | typ. 120 mA |
| Electrical isolation: | 500 V (E-bus/field potential) |
| Current consumption power contacts: | typ. 14 mA + load |
| Bit width in the process image: | 4 outputs + 4 diagnostic inputs |
| Configuration: | no address or configuration setting |
| Special features: | diagnostics: short circuit and open circuit |
| Weight: | approx. 55 g |
| Operating/storage temperature: | -25…+60 °C/-40…+85 °C |
| Relative humidity: | 95 %, no condensation |
| Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos.: | IP 20/variable |
| Pluggable wiring: | for all ESxxxx terminals |
| Approvals: | CE, UL, Ex |