EL1054
EL1054 | 4-channel digital input terminal NAMUR
The EL1054 digital input terminal acquires signals from NAMUR field devices according to EN 60947-5-6. The sensors are supplied with a voltage of 8.2 V and return a diagnosable current signal. In this way, a wire breakage or short-circuit can be detected in addition to the switching state. The LEDs indicate signal or any error states, channel by channel.
| Technology: | NAMUR |
| Specification: | NAMUR DC switching amplifier (IEC 60947-5-6) |
| Signal type: | binary, current input for NAMUR sensors |
| Number of inputs: | 4 |
| Connection technology: | 2-wire |
| Open circuit voltage: | typ. 8.2 V DC |
| “0” signal current: | ≤ 1.2 mA |
| “1” signal current: | ≥ 2.1 mA |
| Switching hysteresis: | typ. 350 µA |
| Short-circuit current: | typ. 7.8 mA |
| Fault detection: | I ≤ 200 µA (cable break), I ≥ 7.0 mA (short circuit) |
| Max. switching frequency: | 5 kHz (duty factor 50 %) |
| Internal resistance: | according to I/V curve IEC 60947-5-6 |
| Distributed clocks: | – |
| Supply voltage electronics: | 24 V DC (via power contacts) |
| Current consumption E-bus: | typ. 50 mA |
| Electrical isolation: | 500 V (E-bus/field potential) |
| Special features: | integrated reverse polarity protection |
| Weight: | approx. 60 g |
| Operating/storage temperature: | 0…+55 °C/-25…+85 °C |
| Relative humidity: | 95 %, no condensation |
| Vibration/shock resistance: | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission: | conforms to EN 61000-6-2/EN 61000-6-4 |
| Protect. class/installation pos.: | IP 20/variable |
| Pluggable wiring: | for all ESxxxx terminals |
| Approvals/markings: | CE, UL, ATEX, IECEx |
| ECCN: | |
| Country of Origin: | |
| EAN: | |
| Weight: | 0.00 kg |
| Length: | 0.00 m |
| Width: | 0.00 m |
| Height: | 0.00 m |