Article image EKM1101

Beckhoff EKM1101

EKM1101 | EtherCAT Coupler with ID switch and diagnostics

On Request. Please send us an email to inquire the price and avaliability.
"ucnguBrctvdgcxgt0eqo"

Description

The EKM1101 EtherCAT Coupler connects the ELMxxxx EtherCAT measurement modules with EtherCAT. Such a station consists of an EKM1101 coupler, any number of EtherCAT Terminals and a bus end cap or an EtherCAT extension such as EK1110 or EK1122. The coupler converts the passing telegrams from Ethernet 100BASE-TX to E-bus signal representation.

Technical parameters

Task within EtherCAT system: coupling of EtherCAT Terminals (ELxxxx) to 100BASE-TX EtherCAT networks, with identity verification
Data transfer medium: Ethernet/EtherCAT cable (min. Cat. 5), shielded
Distance between stations: max. 100 m (100BASE-TX)
Number of EtherCAT Terminals: up to 65,534
Type/number of peripheral signals: max. 4.2 GB addressable I/O points
Number of configurable IDs: 256
Protocol: EtherCAT
Delay: approx. 1 µs
Data transfer rates: 100 Mbit/s
Bus interface: 2 x RJ45
Power supply: 24 V DC (-15 %/+20 %)
Current consumption E-bus:
Current consumption from US: 50 mA + (∑ E-bus current/4)
Current consumption from UP: 50 mA + load
Current supply E-bus: 2000 mA
Power contacts: max. 24 V DC/max. 2 A
Special features: electrically isolated output voltages, reverse polarity protection, diagnostics of supply and output voltages
Electrical isolation: 500 V (power contact/supply voltage/EtherCAT)
Weight: approx. 450 g
Operating/storage temperature: -25…+60 °C/-40…+85 °C
Relative humidity: 95 %, no condensation
Vibration/shock resistance: conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission: conforms to EN 61000-6-2/EN 61000-6-4
Protect. class/installation pos.: IP 20/variable
Approvals/markings: CE

Logistic parameters

ECCN:
Country of Origin:
EAN:
Weight: 0.00 kg
Length: 0.00 m
Width: 0.00 m
Height: 0.00 m