Pepperl+Fuchs 043692

KFD0-TT-Ex1

Thermocouple Converter

По запросу. Пожалуйста, отправьте нам письмо, чтобы узнать цену и наличие.
"ucnguBrctvdgcxgt0eqo"

Описание

1-channel isolated barrier, 24 V DC supply (loop powered), Thermocouple input, Output 4 mA .. 20 mA, Internal cold junction compensation, Sensor breakage detection, DIP switch selectable rangespa. This isolated barrier is used for intrinsic safety applications. It is a loop-powered isolator that converts thermocouple inputs in the hazardous area to a 4 mA .. 20mA signal in the safe area. The internal cold junction compensation can be bypassed by using terminals 1 and 3. The output current is linear to input voltage, not proportional to temperature. Zero, span, and burnout detection are field-configurable.

Технические характеристики

Signal type: Analog input
Rated voltage: 12 ... 35 V DC loop powered
Power dissipation: 0.4 W
Connection side: field side
Connection: terminals 1+, 2-, 3- thermocouple E, J, K, N, R, S or T, cold junction referenced to 0 °C (32 °F)
Lead resistance: max. 100 Ω per line
Current: lead monitoring ON: ≤ 15 nA; OFF: ≤ 1 nA
Connection side: control side
Connection: terminals 9+, 8-
Load: (U -12 V) / 0.02 A
Current output: 4 ... 20 mA , limited to ≤ 35 mA
Fault signal: downscaling ≤ 3 mA , upscaling ≥ 22 mA
Measurement range: span 4 ... 100 mV, zero point -12 ... 60 mV , both adjustable
Deviation: After calibration: 0.1 % of full-scale value ± 1 K for the cold junction
Deviation: Temperature effect: temperature deviation 0.015 % of the span/K or 1.5 µV/K cold junction ± 2 K (calibrated at Tamb = 20 °C (68 °F))
Deviation: Influence of supply voltage: 6.5 ppm/V
Characteristic curve: the output voltage is linearly proportionate to the input voltage (not to temperature)
Rise time: 250 ms
Input/Output: safe isolation according to EN 50178, rated insulation voltage 253 Veff
Control elements: DIP-switch rotary switch
Configuration: via DIP switches via rotary switch
Labeling: space for labeling at the front
Electromagnetic compatibility: Directive 2014/30/EU: EN 61326-1:2013 (industrial locations)
Insulation coordination: EN 50178
Galvanic isolation: EN 50178
Degree of protection: IEC 60529
Ambient temperature: -20 ... 60 °C (-4 ... 140 °F)
Degree of protection: IP20
Connection: screw terminals
Mass: approx. 150 g
Dimensions: 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mounting: on 35 mm DIN mounting rail acc. to EN 60715:2001
EU-Type Examination Certificate: ZELM 00 ATEX 0035
Electromagnetic compatibility: Marking: II (1)GD [EEx ia] IIC
Electromagnetic compatibility: Voltage: 16.1 V
Electromagnetic compatibility: Current: 0.8 mA
Electromagnetic compatibility: Power: 3.2 mW
Output: Maximum safe voltage: 60 V (Attention! The rated voltage can be lower.)
Certificate: TÜV 01 ATEX 1777 X
Output: Marking: II 3G Ex nA II T4
Galvanic isolation: Input/Output: safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity: Directive 2014/34/EU: EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
CSA approval: Control drawing: 116-0132
Supplementary information: Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Логистические характеристики

ТН ВЭД:
Страна происхождения: SG
EAN:
Вес: 0,00 kg
Длина: 0,00 m
Ширина: 0,00 m
Высота: 0,00 m